background image

2604

5

GB

COMBUSTION ADJUSTMENT 

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjust-
ment and testing must be carried out observing the instruction manual of the boiler, including verifica-
tion of the CO and CO

2

 concentration in the flue gases, their temperatures and the average

temperature of the water in the boiler.

To suit the required appliance output, fit the nozzle then adjust the pump pressure and the air damper
opening in accordance with the following schedule.

The values shown in the table are measured on a CEN boiler (as per EN 267).
They refer to 12.5% CO

2

 at sea level and with light oil and room temperature of 20 °C.  

 

RECOMMENDED NOZZLES :

Monarch type R - NS;

Delavan type W - A - E

Steinen type H - Q

;

Danfoss type H - B

Angle

:

60° :

in most cases. 

80° :

in case of flame detachment, during ignitions at low tem-
peratures.

 

PUMP PRESSURE

12 bar :

the pump leaves the factory set at this value.

14 bar : improves flame retention; it is therefore suitable for ignitions at

low temperatures.

 

COMBUSTION HEAD SETTING

This is done when fitting the nozzle, with the blast tube

removed. It depends on the output of the burner and is car-
ried out by rotating the regulating rod, till the terminal plane
of the blast tube is level with the set-point, as indicated in
the schedule.  

Nozzle

Pump pressure

Burner output

Comb. head 

adjustment

Air damper

adjustment

GPH

Angle

bar

kg/h ± 4%

Set-point

Set-point

0.40

80°

12

1.6

0

2.7

0.50

60° / 80°

12

2.0

1

3.3

0.60

60° / 80°

12

2.4

2

4

0.65

60° / 80°

12

2.6

3

5,5

0.75

60°

12

3.0

4

7

1

2

3

4

1

2

3

D5496

1

3

5

In the sketch on the left, the combustion
head is set for an output of  0.60 GPH at
12 bar, while the shutter is level with set-
point  2, as required by the above sche-
dule.

Blast tube

Regulating rod

Shutter

Terminal plane of the blast tube

Summary of Contents for 3742693

Page 1: ...2902604 1 Installation use and maintenance instructions O Oil burner CODE MODEL TYPE 3742693 G3X 450 M1 GB GR One stage operation...

Page 2: ...er Secondary 8 kV 16 mA Pump Pressure 7 15 bar Absorbed electrical power 0 115 kW 1 Return line 2 Suction line 3 Gauge connection 4 Pump pressure regulator 5 Vacuum gauge connection 6 Screws fixing ai...

Page 3: ...115 79 194 130 4 5 11 164 D6219 180 75 72 150 4 5 89 109 It is necessary that the insulating gasket 9 fig 1 is placed between the boiler door and the burner flange This insulating gasket has six holes...

Page 4: ...leakage of the valve PRIMING THE PUMP Start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before repeating the operation A filter...

Page 5: ...h the ignition trans former on a plug in support TESTING Check the shut down of the burner by opening the thermostats ATTENTION Do not connect burner s grounding to failure indicator terminal This may...

Page 6: ...in case of flame detachment during ignitions at low tem peratures PUMP PRESSURE 12 bar the pump leaves the factory set at this value 14 bar improves flame retention it is therefore suitable for igniti...

Page 7: ...not advisable for ignitions at low temperatures In any case do not bring the combustion head setting more than one point away from that indicated in the schedule One set point corresponds to 3 turns o...

Page 8: ...below 8 C increase the pressure to 14 bar 4 COMBUSTION HEAD SETTING Regulate the combustion head one set point further ahead than indicated in the instructions Example the instructions require to set...

Page 9: ...GR E HNIKA CE EMC 89 336 E 92 42 E 19 35 kW 1 6 3 kg h diesel 6 mm2 s 20 C 230 V 10 50 Hz 0 7A 2 850 rpm 298 rad s 4 F 8 kV 16 mA 7 15 bar 0 115 kW 1 2 3 4 5 6 7 8 9 10 2 1 4 1 5 D6218 1 2 3 4 8 6 6 7...

Page 10: ...2604 2 GR 0 8 0 0 2 0 4 mbar 1 5 2 2 5 3 kg h 20 25 30 35 kW D5223 0 6 115 79 194 130 4 5 11 164 D6219 180 75 72 150 4 5 89 109 2 D5242 D5891 2 S7386...

Page 11: ...bar 20 sec L i 8 mm i 10 mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 by pass A L i 8 mm i 10 mm 0 0 5 1 1 5 2 3 3 5 35 30 25 20 15 8 6 100 100 100 90 70 30 20 H max 4 m H H max 4 m min 0 1 m D5616 D5617 D...

Page 12: ...2604 4 GR 50V 6A max N L M 1 mm2 530SE 230V 50Hz N L 230V 0 5A max 1 2 3 4 5 6 7 8 9 530SE T T 1 N 2 L D5228 M A 1 2 L...

Page 13: ...20 C Monarch R NS Delavan W A E Steinen H Q Danfoss 60 80 12 bar 14 bar GPH bar kg h 4 0 40 80 12 1 6 0 2 7 0 50 60 80 12 2 0 1 3 3 0 60 60 80 12 2 4 2 4 0 65 60 80 12 2 6 3 5 5 0 75 60 12 3 0 4 7 1...

Page 14: ...2604 6 GR 1 6 mm 2 o CO2 CO2 1 3 1 2 3 6 D5497 B A D5780 B 4 2 2 5 mm 4 0 3 mm D5230 C C...

Page 15: ...2604 7 GR 8 C F 1 2 M Delavan A E Steinen H Danfoss H 3 12 bar 8 C 14 bar 4 2 3 5 BACCARACH 1 12s D5229 12s 5s 2 2 5 mm 4 0 3 mm D5794 C...

Page 16: ......

Reviews: