BURNER START-UP CYCLE
ADJUSTMENTS, TO AVOID FLAME - DETACHMENT, AT BURNER - IGNITION
This inconvenience can occur, when the temperature of the gas-oil decreases below +8 °C.
1)
CORRECT POSITIONING OF THE ELECTRODES
2) NOZZLE: ATOMIZING
CONE
Choose empt ies or semi-empt ies cones; Delavan type A - E; Steinen type H; Danfoss type H.
3)
PUMP - SETTING
The pump is factory set, at a pressure of 12 bar.
When the temperature of the light oil decreases below +8 °C, increase the pressure to 14 bar.
4) COMBUSTION-HEAD
SETTING
Regulate the combustion-head one set-point further ahead than indicated in the instructions.
Example:
the instructions require to set the combustion-head on set-point 2.
Instead, the setting is made on set-point 3.
5)
FAN - AIR DAMPER ADJUSTMENT
Adjust the air damper of the fan, such as to obtain a smoke-number not inferior to 1.
(i.e. a combustion with the lowest possible excess-air).
Normal
Lock-out, due to failure to light
Thermostat
Motor
Ignition transformer
Valve
Flame
Lock-out lamp
~
12s
D5229
~
12s
~
5s
2 – 2.5
mm
4 ±
0.3 mm
IMPORTANT:
THESE DIMENSIONS
MUST BE OBSERVED
D5230
C