TECHNICAL DATA
◆
Burner with CE marking in conformity with EEC directives: EMC89/336/EEC, Low Voltage 73/23/EEC,
Machines 98/37/EEC and Efficiency 92/42/EEC.
◆
The burner meets protection level of IP 40, EN 60529.
TYPE
445T1
Thermal power – output
28 – 60 kW
–
2.3 – 5 kg/h
Fuel
Light oil, max. viscosity at 20 °C: 6 mm
2
/s
Electrical supply
Single phase,
230 V
±
10%
~
50Hz
Motor
Run current 0.75 A – 2850 rpm – 298 rad/s
Capacitor
4
µ
F
Ignition transformer
Secondary 8 kV – 16 mA
Pump
Pressure 7 – 15 bar
Absorbed electrical power
0.130 kW
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air-damper
7 – Hydraulic jack with air-damper
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Combustion head adjustment screw
EQUIPMENT
Quantity
Description
2
1
4
1
1
1
Flexible oil pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
to be fixed to boiler
Hinge
Screw and nuts for flange
Grommet
Fig. 1
5
D5553
1
2
3
4
8
6
6
7
9
10