BURNER START-UP CYCLE DIAGNOSTICS
During start-up, indication is according to the followin table:
OPERATING FAULT DIAGNOSTICS
The control box has a self-diagnostic system, which easily allows identifying the operating faults (
RED
LED
signal).
ITo use this function, wait at least ten seconds from the safety lock out, and then press the reset button for
a minimum of 3 seconds.
After releasing the button, the RED LED starts flashing as shown in the diagram below.
The pulses of the LED constitute a signal spaced by approximately 3 seconds.
The number of pulses will provide the information on the possible faults, according to the table below:
COLOUR CODE TABLE
Sequences
Colour code
Pre-purging
Ignition phase
Operation, flame ok
Operating with weak flame signal
Electrical supply lower than ~ 170V
Lock-out
Extraneous light
Key:
Off
Yellow
Green
Red
SIGNAL
PROBABLE CAUSE
2 flashes
The flame does not stabilise at the end of the safety time:
√ faulty ionisation probe;
√ faulty or soiled gas valves;
√ neutral/phase exchange;
√ faulty ignition transformer;
√ poor burner regulation (insufficient gas).
3 flashes
Min. air pressure switch does not close:
√ air pressure switch faulty;
√ air pressure switch incorrectly regulated;
√ max. air pressure switch triggered (if installed).
4 flashes
Min. air pressure switch does not open or light in the chamber before firing:
√ air pressure switch faulty;
√ air pressure switch incorrectly regulated.
7 flashes
Loss of flame during operations:
√ poor burner regulation (insufficient gas);
√ faulty or soiled gas valves;
√ short circuit between ionisation probe and earth.
8 flashes
√ Not used.
10 flashes
√ Wiring error or internal fault.
RED LED on
wait at least 10 s
Press button
for > 3 s
Signal
Signal
Interval
3 s