(1) The control box 22)(A)p.8 is fitted with a disc  which rotates during the firing programme, which can be seen through the transparent lock-out reset button. When

the burner does not fire or comes to halt following a fault, the symbol which appears behind the reset button indicates the type of problem.

(2) The fuse is located in the rear part of the control box 22)(A)p.8. A pull-out fuse is also available as a spare part which can be fitted after breaking the tag on the

panel which holds it in place.

SYMBOL 

(1)

FAULT

PROBABLE CAUSE

SUGGESTED REMEDY

The burner does not start

1

- No electrical power supply  . . . . . . . . . . . . . . . . . . . . . . . . . Close all switches - Check connections

2

- A limiter or safety control device is open. . . . . . . . . . . . . . . Adjust or replace

3

- Control box lock-out  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset control box

4

- Control box fuses blown  . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace 

(2)

5

- Erroneous electrical connections  . . . . . . . . . . . . . . . . . . . . Check connections

6

- Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace

7

- No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Open the manual valves between meter and 

train

8

- Mains gas pressure insufficient . . . . . . . . . . . . . . . . . . . . . . Contact your GAS COMPANY

9

- Minimum gas pressure switch fails to close  . . . . . . . . . . . . Adjust or replace

10 - Air pressure switch in operating position  . . . . . . . . . . . . . . Adjust or replace
11 - Cam I I servomotor contact does not operate . . . . . . . . . . . Adjust cam I I or replace servomotor

control box terminals 11-8

The burner does not start 
and a function lock out occurs

12 - Flame simulation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace control box
13 - Defective capacitor (RS 28/M)
14 - Defective motor remote control switch (RS 38-50/M) . . . . . Replace
15 - Defective electrical motor  . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
16 - Motor protection tripped (RS 38-50/M) . . . . . . . . . . . . . . . . Reset thermal cut-out when third phase is re-

connected

The burner starts 
but stops at maximum 
gate valve setting

17 - Cam I servomotor contact does not operate . . . . . . . . . . . . Adjust cam I or replace servomotor

control box terminals 9-8

The burner starts 
and then locks out

Air pressure switch inoperative due to
insufficient air pressure:

18 - Air pressure switch adjusted badly . . . . . . . . . . . . . . . . . . . Adjust or replace
19 - Pressure switch pressure point pipe blocked  . . . . . . . . . . . Clean
20 - Head wrongly adjusted . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust

The burner starts and 
then locks out

21 - Fault in flame detection circuit. . . . . . . . . . . . . . . . . . . . . . . Replace control box

The burner stays 
in the pre-purge stage

22 - Cam I I I servomotor contact does not operate . . . . . . . . . . Adjust cam I I I or replace servomotor

control box terminals 10-8

After pre-purge and 
safety time, 
the burner goes to lock-out 
and the flame does not appear

23 - The solenoid VR allows little gas through . . . . . . . . . . . . . . Increase
24 - Solenoid valves VR or VS fail to open  . . . . . . . . . . . . . . . . Renew the coil or rectifier panel
25 - Gas pressure too low  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Increase pressure at governor
26 - Ignition electrode wrongly adjusted . . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p.14
27 - Electrode grounded due to broken insulation . . . . . . . . . . . Replace
28 - High voltage cable defective . . . . . . . . . . . . . . . . . . . . . . . . Replace
29 - High voltage cable deformed by high temperature . . . . . . . Replace and protect
30 - Ignition transformer defective  . . . . . . . . . . . . . . . . . . . . . . . Replace
31 - Erroneous valve or transformer electrical connections . . . . Repeat connection
32 - Control box defective  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
33 - A cock down-line of the gas train is closed . . . . . . . . . . . . . Open
34 - Air in pipework. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  Bleed air

The burner goes to lock-out 
right after flame appearance

35 - The solenoid VR allows little gas through . . . . . . . . . . . . . . Increase
36 - Ionisation probe wrongly adjusted. . . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p.14
37 - Faulty electrical connections for probe . . . . . . . . . . . . . . . . Repeat connection
38 - Insufficient ionisation (less than 6 µA). . . . . . . . . . . . . . . . . Check probe position
39 - Probe grounded  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Withdraw or replace cable
40 - Max. gas pressure switch operates. . . . . . . . . . . . . . . . . . . Adjust or replace
41 - Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace

The burner repeats 
the starting cycle 
without lock out

42 - Mains gas pressure is near the value to which the . . . . . . . Reduce operating pressure

min. gas pressure switch gas is adjusted. The

of minimum gas pressure

repeated drop in pressure which follows valve

switch.

opening causes temporary opening of the pressure

Replace gas filter.

switch itself, the valve immediately closes and the
burner comes to a halt. Pressure increases again, the
pressure switch closes again and the firing cycle is
repeated. The sequence repeats endlessly.

Lock out without symbol indication 43 - Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace control box

During operation, the 
burner stops in lock out

44 - Probe or ionisation cable grounded  . . . . . . . . . . . . . . . . . . Replace worn parts
45 - Fault on air pressure switch  . . . . . . . . . . . . . . . . . . . . . . . . Replace
46 - Max. gas pressure switch operates. . . . . . . . . . . . . . . . . . . Adjust or replace

Lock out when burner stops

47 - Flame remains in combustion head  . . . . . . . . . . . . . . . . . . Eliminate persistence of flame

or flame simulation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . or replace control box

Ignition with pulsation

48 - Poorly adjusted head  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust, see page 17
49 - Ignition electrode wrongly adjusted . . . . . . . . . . . . . . . . . . . Adjust, see fig. (C),page 14
50 - Poorly adjusted fan air gate: too much air. . . . . . . . . . . . . . Adjust
51 - Output during ignition phase is too high  . . . . . . . . . . . . . . . Reduce

P

1

Summary of Contents for 3781012

Page 1: ...as burners Br leurs gaz air souffl 2915608 4 02 2008 CODICE CODE MODELLO MODELL MODEL MODELE TIPO TYP TYPE 3781012 RS 28 M 824 T1 3781013 RS 28 M 824 T1 3781412 RS 38 M 825 T1 3781413 RS 38 M 825 T1 3...

Page 2: ......

Page 3: ...ieb sanleitung der Heizkessels ausgef hrt werden einschlie lich Kontrolle der Konzentration von CO und CO2 in den Abgasen ihrer Temperatur und der mittlenen Kesseltemperatur D CONTENTS TECHNICAL DATA...

Page 4: ...1 6 6 9 7 7 2 10 6 FUNZIONAMENTO Intermittente min 1 arresto in 24 ore Questi bruciatori sono adatti anche al funzionamento continuo se ven gono equippaggiati con l apparecchiatura Landis LGK 16 333...

Page 5: ...haltung in 24 Std Wenn dieser Brenner mit dem Gasfeuerungsautomaten Landis Gyr LGK 16 333 A27 ausgestattet ist ist er auch f r den Dauerbetrieb gee ignet Die elektrische Verdrahtung des Brenners bleib...

Page 6: ...7 7 2 10 6 OPERATION On Off 1 stop min each 24 hours This burner is also fitted for the continuos operation if it is equipped with the control box LANDIS type LGK 16 333 A27 interchangeable with the b...

Page 7: ...max 2 mbar 7 5 11 1 6 6 9 7 7 2 10 6 FONCTIONNEMENT Intermittent 1 arr t min en 24 heures Ce br leurs est appropri s aussi pour le service permanent s il est quip s avec le bo tier LANDIS type LGK 16...

Page 8: ...ressostato aria 26 Staffa per l applicazione del regolatore di potenza RWF40 27 Spina presa sul cavo della sonda di ionizza zione Vi sono due possibilit di blocco del bruciatore BLOCCO APPARECCHIATURA...

Page 9: ...trical connection 24 Air gate valve 25 Pipe connection the fan air inlet to the air pressure switch 26 Bracket for mounting the power regulator RWF40 27 Plug socket on ionisation proble cable Two type...

Page 10: ...676 Riportiamo in B diametro e lunghezza della camera di combustione di prova Esempio Potenza 350 Mcal h diametro 50 cm lunghezza 1 5 m CALDAIE COMMERCIALI L abbinamento bruciatore caldaia non pone pr...

Page 11: ...e firing rates were set in relation to special test boilers according to EN 676 regulations Figure B indicates the diameter and length of the test combustion chamber Example Output 350 Mcal h diameter...

Page 12: ...alla quale si desidera funzioni il bruciatore trovare nella tabella relativa al bruciatore con siderato il valore di potenza pi vicino al val ore desiderato Leggere sulla destra colonna 1A o B la pre...

Page 13: ...er in question Read off the corresponding output on the left Example RS 28 M Maximum output operation Natural gas G 20 PCI 10 kWh Nm3 Gas ring 2 B p 16 adjusted as indicated in diagram C p 16 Gas pres...

Page 14: ...ati come in C Separare quindi la testa di combustione dal resto del bruciatore fig B togliere la vite 14 ed estrarre il cofano 15 sganciare lo snodo 4 dal settore graduato 5 togliere le viti 2 dalle d...

Page 15: ...hrough the blast tube opening to make sure that the flame sensor probe and the ignition electrode are correctly set in position as shown in C Now detach the combustion head from the burner fig B remov...

Page 16: ...iva di pulsazioni B La potenza MIN del bruciatore com presa nei valori della tabella D Regolazione aria Vale quanto detto per il caso precedente seg uire il diagramma C Regolazione gas La ghiera 2 B v...

Page 17: ...ressure indi cated on page 12 and if the ring 2 B is not fully open it can be opened wider by 1 or 2 notches Continuing with the previous example page 12 indicates that for burner RS 38 M with output...

Page 18: ...a monte del filtro L Rampa gas fornita a parte con il codice indicato in tab C L1 A cura dell installatore LEGENDA TABELLA C C T Dispositivo controllo tenuta valvole gas 8 9 Rampa priva del dispositiv...

Page 19: ...rd issue burner gasket with flange 11 Gas adjustment butterfly valve 12 Burner 13 Gas valve 8 9 leak detection control device In accordance with EN 676 Standards gas valve leak detection control devic...

Page 20: ...7 C del bruciatore vanno fatti passare dai passacavi for niti a corredo da inserire nei fori della piastrina di destra o di sinistra dopo aver svitato le viti 8 aperto la piastrina nelle parti 9 e 10...

Page 21: ...in rubber sheath use at least H05 RR F All the wires to connect to the burner terminal strip 7 C must enter through the supplied fair leads which must be fitted into the relevant holes in the left ha...

Page 22: ...di funzionamento TL Telecomando di limite ferma il bruciatore quando la temperatura o la pressione in caldaia raggiunge il val ore prestabilito TS Telecomando di sicurezza interviene in caso di TL gu...

Page 23: ...te lock out signal S1 Remote lock out signal of leak detection control device TR High low mode load remote control system controls operating stages 1 and 2 TL Load limit remote control system shuts do...

Page 24: ...20 A p 8 Serve ad evitare la bruciatura del motore per un forte aumento dell assorbimento dovuto alla mancanza di una fase Se il motore alimentato a stella 400 V il cur sore va posizionato sul MIN Se...

Page 25: ...als AL AL1 to replace the remote control TL or to control an external device LAYOUT F Calibration of thermal cut out 20 A p 8 This is required to avoid motor burn out in the event of a significant inc...

Page 26: ...amma I 90 Limita la rotazione verso il massimo Con il bru ciatore funzionante alla potenza MAX la farfalla del gas deve risultare tutta aperta 90 Camma I I 0 Limita la rotazione verso il minimo A bruc...

Page 27: ...ngle of rotation of the servomoteur is equal to the angle on the graduated sector con trolling the gas butterfly valve The servomotor rotates through 90 degrees in 24 seconds Do not alter the factory...

Page 28: ...ccensione deve essere uguale o inferiore a 300 kW con ts 2 s 200 kW con ts 3 s Per misurare la potenza all accensione scollegare la spina presa 27 A p 8 sul cavo della sonda di ionizzazione il bruciat...

Page 29: ...able the burner will fire and then go into lock out after the safety time has elapsed Perform 10 firings with consecutive lock outs On the meter read the quantity of gas burned This quantity must be e...

Page 30: ...ella che deve portare la serranda dell aria alla totale chiusura 4 POTENZE INTERMEDIE Regolazione del gas Non occorre alcuna regolazione Regolazione dell aria Premere un poco il pulsante 2 A p 28 aume...

Page 31: ...la came I I I et enfin reporter le servomoteur en position de puis sance MIN avec le bouton diminution de la puissance Pour le r glage ventuel de la came I I I retirer le couvercle 1 enclench par pres...

Page 32: ...A B Eseguire la regolazione del pressostato gas di massima dopo aver effettuato tutte le altre regolazioni del bruciatore con il pressostato gas di massima regolato a fine scala B Con il bruciatore fu...

Page 33: ...H B Adjust the maximum gas pressure switch after having performed all other burner adjustments with the maximum gas pressure switch set to the end of the scale B With the burner operating at MAX outpu...

Page 34: ...rretta posizione dei pressostati aria e gas di massima Se la temperatura o la pressione bassa per cui il telecomando TR chiuso il bruciatore aumenta progressivamente la potenza fino al valore MAX trat...

Page 35: ...ntr ler la pr sence de la flamme et la bonne position des pressostats air et gaz maximum Si la temp rature ou la pression sont basses et que par cons quent la t l commande TR est ferm e le br leur aug...

Page 36: ...ntate nei cinematismi che comandano la serranda aria e la farfalla del gas Cos pure bloccate devono essere le viti che fissano i cavi nella morsettiera del bruciatore Pulire esternamente il bruciatore...

Page 37: ...s wear or loose screws in the mechanisms controlling the air gate valve and the gas butterfly valve Also make sure that the screws securing the electrical leads in the burner connections are fully tig...

Page 38: ...tti 10 8 apparecchiatura Superata la preventilazione ed il tempo di sicurezza il bruciatore va in blocco senza apparizione di fiamma 23 L elettrovalvola VR fa passare poco gas Aumentarlo 24 L elettrov...

Page 39: ...abschaltung des Brenners nach der Vorbel ftung und der Sicherheitszeit ohne Flammenbildung 23 Ungen gender Gasflu durch das Magnetventil VR Steigern 24 Magnetventil VR bzw VS ffnet nicht Spule oder Gl...

Page 40: ...servomotor control box terminals 10 8 After pre purge and safety time the burner goes to lock out and the flame does not appear 23 The solenoid VR allows little gas through Increase 24 Solenoid valves...

Page 41: ...Apr s la pr ventilation et le temps de s curit le br leur se bloque sans apparition de flamme 23 Electrovanne VR fait passer peu de gaz Augmenter 24 L lectrovanne VR ou VS ne s ouvre pas Remplacer bo...

Page 42: ......

Page 43: ......

Page 44: ...RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www rielloburners com Con riserva di modifiche nderungen vorbehalten Subject to modifications Sous r serve de modifications...

Reviews: