6
TECHNICAL DATA
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2) Pressure at test point 8)(A)p.8, with zero pressure in the combustion chambre, with open gas ring 2)(B)p.16 an maximum burner output
(3) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output.
VARIANTS:
ACCESSORIES
(optional):
• KIT FOR LPG OPERATION:
The kit allows the RS 28-38-50/M burners to operate on LPG.
• VIBRATION REDUCTION KIT
•
OUTPUT POWER REGULATOR KIT:
Under modulating operation, the burner automatically adapts to one of an infinite number of firing rates
between the low and high flame output position, thus ensuring stable operating conditions in terms of temperature or pressure. Two components
should be ordered: • Power regulator to install to the burner; • probe to install to the boiler.
•
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valves, pressure governor and filter):
see page 19.
MODEL
RS 28/M
RS 38/M
RS 50/M
TYPE
824 T1
825 T1
826 T1
OUTPUT
(1)
MAX.
kW
163 - 325
140 - 280
232 - 440
200 - 378
290 - 580
249 - 499
Mcal/h
MIN.
kW
52
45
70
60
85
73
Mcal/h
FUEL
NATURAL GAS: G20 - G21 - G22 - G23 - G25
G20
G25
G20
G25
G20
G25
- Net calorific value
kWh/Nm
3
Mcal/Nm
3
10
8,6
8,6
7,4
10
8,6
8,6
7,4
10
8,6
8,6
7,4
- Absolute density
kg/Nm
3
0,71
0,78
0,71
0,78
0,71
0,78
- Max. delivery
Nm
3
/h
32
38
44
51
58
68
- Pressure at max. delivery
(2)
mbar
7,5
11,1
6,6
9,7
7,2
10,6
OPERATION
• On-Off (1 stop min each 24 hours).
This burner is also fitted for the continuos operation, if it is equipped
with the control box LANDIS type LGK 16.333 A27 (interchangeable
with the burner control box Landis LFL 1.333).
• Progressive two-stage or modulating by kit (see ACCESSOIRES).
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATUR
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
Hz
230 ~ +/- 10%
50 - single-phase
230 - 400 with neutral ~ +/- 10%
50 - three-phase
ELECTRIC MOTOR
rpm
W
V
A
2800
250
220 - 240
2,1
2800
450
220/240 - 380/415
2 - 1,2
2800
650
220/240 - 380/415
3 - 1,7
MOTOR CAPACITOR
µF / V
8/450
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
ELECTRICAL POWER CONSUMPTION
W max
370
560
750
ELECTRICAL PROTECTION
IP 44
IN CONFORMITY WITH EEC DIRECTIVES
90/396 - 89/336 - 2004/108 - 73/23 - 2006/95 - 92/42
NOISE LEVELS
(3)
dBA
68
70
72
APPROVAL
CE
0085AQ0709
BURNER
RS 28/M
RS 38/M
RS 50/M
Blast tube lenght mm
216
351
216
351
216
351
BURNER
RS 28/M
RS 38/M
RS 50/M
Output kW
95 ÷ 325
115 ÷ 440
140 ÷ 580
Code
3010079
3010080
3010081
3010082
3010083
3010084
BURNER
RS 28/M
RS 38/M
RS 50/M
Output kW
81 ÷ 325
105 ÷ 440
116 ÷ 580
Code
3010198
3010199
3010200
PARAMETER TO BE CHECKED
PROBE
POWER REGULATOR
Range
Type
Code
Type
Code
Temperature
- 100...+ 500°C
PT 100
3010110
RWF40
3010212
Pressure
0...2,5 bar
0...16 bar
Output probe
4...20 mA
3010213
3010214
Important:
The installer is responsible for the addition of any safety device not forseen in the present manual.
GB
COUNTRY
CATEGORY
IT-AT-GR-DK-FI-SE
II
2H3B/P
ES-GB-IE-PT
II
2H3P
NL
II
2L3B/P
FR
II
2Er3P
DE
II
2ELL3B/P
BE
I
2E(R)B,
I
3P
LU
II
2E3B/P