3209

6

 

AIR DAMPER ADJUSTMENT

The regulation  of  the air-rate is made by adjusting the air

damper  (1), after loosing the screws  (2).
The settings indicated in the schedule refer to the burner

with its metal cover fitted and the combustion chamber with

“zero” depression.

These regulations are purely indicative. Each installation how-

ever, has its own unpredictable working conditions: actual
nozzle output; positive or negative pressure in the combus-

tion-chamber, the need of excess air, etc. 
All these conditions may require a different air-damper set-

ting.

It is important to take account of the fact that the air
output of the fan differs according to whether the burn-
er has its metal cover fitted or not.  
Therefore we recommended to proceed as follows:

–  adjust the air damper as indicated in the schedule (3);
–  mount the cover, simply by means of the upper screw;
–  check smoke number;
–  should it become necessary to modify the air output, remove the cover by loosening the screw,

adjust the air damper, remount the cover and finally recheck the smoke number.

ELECTRODE SETTING

BURNER START-UP CYCLE

2

1

2

D5675

3

Attention:

Before assembling or removing the

nozzle, loose n  the screw 

(A)

 an d

move the electrodes ahead.

2 – 2.5

 mm

4

± 

0.3 mm

IMPORTANT:
THESE  DIMENSIONS
MUST BE OBSERVED

D5230

A

Normal

Lock-out, due to light-failure

Thermostat

Motor

Ignition transformer

Valve

Flame

Lock-out lamp

~

 

12s

D5229

~

 

12s

~

 

5s

Summary of Contents for 443T58

Page 1: ...2903209 0 Installation use and maintenance instructions Light oil kerosene burner One stage operation CODE BOULTER CODE MODEL TYPE 3744364 8 716 111 549 COH 110 443T58...

Page 2: ...ad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Kerosene maximum pressure 10 bar 145 psi Light oil maximum pressure 15 bar 218 psi Absorbed electrical power 0 16 kW 1 Return line 2 S...

Page 3: ...L DIMENSIONS BURNER FIXING 0 6 0 2 0 4 Fuel output kg h Thermal power kW D7263 Pressure in the combustion chamber mbar 0 8 0 1 5 2 2 5 20 25 30 3 3 5 35 40 Flange Burner 272 219 130 28 4 5 84 233 11 1...

Page 4: ...ally the flexible pipes conditions Using kerosene they have t o be replaced at least every 2 years A metal bowl filter with replaceable micronic filter must be fitted in the oil supply pipe PRIMING PU...

Page 5: ...box 530SE Valve RUN OF THE ELECTRICAL CABLE 1 Grommet N Neutral 2 Cable clamp L Phase 3 Terminal block Burner earth A 3 2 1 D7261 Black 4 pin plug 4 pole socket ATTENTION Do not swap neutral and phase...

Page 6: ...type ES only for kerosene Angle 60 in most cases 80 in case of flame detachment during ignitions at low temperatures PUMP PRESSURE The pump leaves the factory set for kerosene working 10 bar maximum...

Page 7: ...hat the air output of the fan differs according to whether the burn er has its metal cover fitted or not Therefore we recommended to proceed as follows adjust the air damper as indicated in the schedu...

Page 8: ...ed for The manufacturer accepts no liability within or without the contract for any damage caused to people animals and property due to installation adjustment and maintenance errors or to improper us...

Page 9: ...s d tach es Ersatzteile Katalog Onderdelencatalogus Oil Kerosene burner Bruciatore di gasolio kerosene Br leur fioul domestique k ros ne l Kerosen Gebl sebrenner Stookoliebrander kerosine MOD COD BOUL...

Page 10: ...NIPPEL NIPPEL C 23 3005786 FLANGE FLANGIA BRIDE FLANSCH FLENS 24 3006552 ELECTRODE BRACKET FASCETTA SUPPORT ELECTRODES ELECTRODEN HALTERUN G ELECTRODENKLEM 25 3005724 NOZZLE HOLDER PORTAUGELLO PORTE G...

Reviews: