FAULTS / SOLUTIONS
Here below you can find some causes and the possible solutions for problems that could cause a failure to
start or a bad working of the burner.
A fault usually makes the lock-out lamp light which is situated inside the reset button of the control box
(4, fig. 1, page 1).
When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the
burner functions correctly, the lock-out can be attributed to a temporary fault.
If however the lock out continues the cause must be determined and the solution found.
WARNING:
The manufacturer cannot accept responsibility for any damage to persons, animals or property due to error
in installation or in the burner adjustment, or due to improper or unreasonable use or non observance of the
technical instruction enclosed with the burner, or due to the intervention of unqualified personnel.
FAULTS
POSSIBLE CAUSES
SOLUTION
The burner will not
start when the ad-
justment thermo-
stat closes.
Lack of electrical supply.
Check presence of voltage in the
L1 - N clamps of the 7 pin plug.
Check the conditions of the fuses.
Check that thermostat limit is not
lock out.
Thermostats are faulty.
Replace them.
The connections in the control box
are wrongly inserted.
Check and connect completely all the
plugs.
Lock-out because of a failure to turn
off (event B page 9).
Call technical assistance.
The burner remains
in the pre-purge
phase.
The flame detector sees strange light
(Led 1 is switched on).
Eliminate the light.
Burner runs normal-
ly in the prepurge
and ignition cycle
and locks out after 5
seconds ca.
The flame detector is dirty.
Clear it.
The flame detector is defective
Change it.
Flame moves away or fails.
Check pressure and output of the fuel.
Check air output.
Change nozzle.
Check the coil of solenoid valve
1st stage.
Yellow flame
Nozzle dirty or worn.
Replace it.
Defect in the air output.
Adjust the air output.
Pump pressure is not correctly set.
Verify the pressure and the output of
the fuel and adjust them according to
the instructions of this manual.
Air suction inlet is clogged.
Clear it.
Obstruction in the exhaust circuit.
Clear it.
Burner starts with an
ignition delay.
The ignition electrodes are wrongly
positioned.
Adjust them according to the
instructions of this manual.
Air output is too high.
Set the air output according to the
instructions of this manual.
Nozzle dirty or worn.
Replace it.