Remove nozzle-holder assembly (1) after loos-
ing screws (2) and nut (3), remove the small ca-
b l e s ( 4 ) f r o m t h e c o n t r o l b o x a n d t h e
photoresistance (6).
➤
Withdraw the small cables (4) from the elec-
trodes, remove the diffuser disc-holder assem-
bly (10) from the nozzle-holder assembly (1)
after loosing screw (3, fig. 12).
➤
Screw the nozzle (11) correctly and tighten
it as shown in figure.
ATTENTION
During the reassembly of the nozzle-holder as-
sembly screw the nut (3) as shown in the figure
below.
4.3
ELECTRODES ADJUSTMENTS (
see fig. 12)
4.4
PUMP PRESSURE
The pump leaves the factory set at 12 bar.
To change it act on pump pressure adjust screw (4, fig. 5, page 4).
S7640
B
Fig. 11
B
3
TIGHTEN WITHOUT MOVING
BACKWARDS TO THE END
D5684
WARNING
Lean the diffuser disc-holder as-
sembly (1) on the nozzle-holder
(2) and lock it by screw (3).
For prospective adjustments
loosen screw (4) and move the
electrodes assembly (5).
ATTENTION
To have access to the electrodes
carry out operation as described in
chapter “4.2 RECOMMENDED
NOZZLES” (page 6).
Fig. 12
4 – 5
mm
4.5
– 0.5 mm
0
1
MEASURES MUST BE
2
3
5
4
D5537
RESPECTED