15
BURNER ADJUSTMENT TABLES
NON-RETROFIT APPLICATIONS
If this burner is being installed in a packaged unit (i.e. Burner comes with a boiler or furnace), follow the
installation and set-up instructions supplied with the heating appliance, as settings will differ from those
shown in this manual.
MODEL F3 BURNER SETUP CHART
MODEL F5 BURNER SETUP CHART
ACTUAL FIRING
RATE 5% ±
NOZZLE
SIZE
PUMP
PRESSURE
US GPH
GPH
PSI
BAR
TURBULATOR
SETTING
AIR DAMPER
SETTING
0.75
.60 x 60/ 80º
145
10
0.0
2.25
0.85
.65 x 60/ 80º
145
10
0.5
2.5
1.00
.85 x 60/ 80º
145
10
1.0
2.75
1.10
1.00 X 60/ 80°
145
10
2.0
3.0
1.25
1.10 x 60/ 80º
145
10
2.5
3.5
1.50
1.25 x 60/ 80º
145
10
3.0
4.25
1.65
1.35 X 60/ 80°
145
10
4.0
6.0
NOTE: The above set up charts are a starting point only. The burner and appliance must be properly set
up using proper combustion testing equipment.
Note: any approved oil burner nozzle type, angle and manufacturer maybe used, as long as input
is corresponding the correct BTU/hr. or US gph input rating of the appliance.
COMBUSTION CHAMBER
Follow the instructions furnished by the boiler/furnace manufacturer. Size retrofit application according to the
appropriate installation codes (e.g. CSA B139 or NFPA #31).
ACTUAL FIRING
RATE 5% ±
NOZZLE
SIZE
PUMP
PRESSURE
US GPH
GPH
PSI
BAR
TURBULATOR
SETTING
AIR DAMPER
SETTING
0.50
.40 x 60º/80º
160
11.0
0.0
2.3
0.60
.50 x 60º/80º
150
10.4
0.5
2.7
0.75
.60 x 60º/80º
150
10.4
1.5
3.4
0.80
.65 x 60º/80º
150
10.4
2.0
3.6
0.95
.75 x 60º/80º
160
11.0
3.0
4.3
Summary of Contents for RIELLO 40 F3