2351
1
GB
Oil burner
G10
CODE
3746412
TYPE
464T1
TECHNICAL FEATURES
n
For use on hot air generator the burner must be fitted with control box type
479SE or 539SE.
n
Burner with CE marking in conformity with EEC directives: EMC89/336/EEC, Low Voltage 73/23/EEC,
Machines 89/392/EEC and Efficiency 92/42/EEC.
n
The burner meets protection level of IP 40, EN 60529.
n
DIN Certification No. : 5G348 / 94 as EN 267.
Thermal power – output
54 – 120 kW
–
4.5 – 10 kg/h
Fuel
Gas oil, max. viscosity at 20
°
C: 6 mm
2
/s (1.5
°
E)
Electrical supply
Single phase,
230 V
±
10%
~
50Hz
Motor
Run current 0.80 A – 2850 rpm – 298 rad/s
Capacitor
4
m
F
Ignition transformer
Secondary 8 kV – 16 mA
Pump
Pressure 7 – 15 bar
Absorbed electrical power
0.170 kW
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air-damper
7 – Hydraulic jack with air-damper
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Combustion head adjustment screw
EQUIPMENT
Quantity
Description
2
1
2
1
1
Flexible pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
Hinge
Screw with two nuts for flange
5
D5668
Fig. 1
1
2
3
4
8
6
7
9
10
6