2352
6
GB
COMBUSTION ADJUSTMENT
In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjust-
ment and testing must be carried out observing the instruction manual of the boiler, including verifica-
tion of the CO and CO
2
concentration in the flue gases, their temperatures and the average
temperature of the water in the boiler.
To suit the required appliance output, fit the nozzle, the settings of the combustion head and the air
damper opening in accordance with the following schedule.
NOZZLES RECOMMENDED:
Monarch type R
Delavan type W - B
Steinen type S - Q
Danfoss type S
COMBUSTION HEAD SETTING
: This is done when fitting the nozzle, with the blast tube
removed. It depends on the output of the burner and is car-
ried out by rotating the regulating rod, till the terminal plane
of the blast tube is level with the set-point, as indicated in
the schedule.
Nozzle
Pump
pressure
Burner
output
Comb. head
adjustment
Air damper adjustment
bar
kg/h
±
4%
1
st
stage
2
nd
stage
GPH
Angle
1
st
2
nd
1
st
2
nd
Set-point
Set-point
Set-point
1.00
60
°
8
14
3.5
4.7
1.5
2.2
2.6
1.10
60
°
8
14
3.8
5.1
1.5
2.4
2.9
1.25
60
°
8
14
4.3
5.8
2.0
2.6
3.2
1.50
60
°
8
14
5.2
7.0
2.5
2.8
3.5
1.75
60
°
8
14
6.0
8.2
3.5
3.0
4.3
2.00
60
°
8
14
6.9
9.3
4.0
3.3
5.0
2.25
60
°
8
13
7.8
10.1
5.0
3.6
6.0
3
1
2
1
For 2.00 - 2.25 GPH nozzles it is
advisable to use, if possible,
full cones.
2
D5680
2
1
3
5
In the sketch on the left, the combustion
head is set for an output of 1.50 GPH at
8/14 bar, while the shutter is level with
set-point 2.5, as required by the above
schedule.
Blast tube
Regulating rod
Shutter
Terminal plane of the blast tube
Summary of Contents for G10I
Page 2: ......