- 19 -
USE
S
WITCHING ON FOR THE FIRST TIME
1) Power on the CPS.
2) If there are Battery Cabinets, insert the fuse in the battery fuse holder isolator (SWBATT)
3)
Close the mains input switch (SWIN) in the back of the CPS. Close the fuse holder isolator (SWBATT) paying due
attention as described in the previous chapter. We recommend reading the paragraph “
CPS – B
ATTERY
C
ABINET
CONNECTION
”
4) After a few moments, the CPS will switch on, the display will light up, there will be a beep and the
icon will start to
flash. The CPS is in stand-by mode: meaning that it is only consuming a small amount of power. The microcontroller
supervising the self-diagnoses is powered; the batteries are charging; and everything is ready for CPS activation.
Battery operation is also in stand-by mode provided that the timer is active.
5) Connect the equipment to the output of the CPS using cables no longer than 10 metres.
WARNING: Do not connect the EnergyShare sockets to devices that absorb more than 10A. For equipment that
exceeds these levels, use the appropriate terminals only.
6) Check which operating mode is set on the display and, if necessary, see the “
C
ONFIGURING OPERATING MODES
”
paragraph to set the required mode. For advanced configurations, set up the CPS with the appropriate configuration
software.
S
WITCHING ON FROM THE MAINS
1) Press the “ON” button for 1 second. After pressing it, all the icons on the display light up for 1 second and the CPS
beeps.
2) Close the output switch (SWOUT) in the back of the CPS.
3) Switch on the equipment connected to the CPS.
When switching on for the first time only:
after 30 seconds, check that the CPS is operating correctly:
1) Simulate a blackout by disconnecting power to the CPS.
2) The load must continue to be powered, the
icon on the display must light up and there must be a beep every
4 seconds.
3) When power is reconnected, the CPS must go back to operating from the mains.
S
WITCHING ON FROM THE BATTERY
1) Hold down the “ON” button for at least 5 seconds. All the icons on the display light up for 1 second.
2) Switch on the equipment connected to the CPS.
S
WITCHING OFF THE
CPS
In order to switch off the CPS, hold down the “STBY” button for at least 2 seconds. The CPS goes back to stand-by mode and
the
icon starts to flash:
1) If the mains power is present, open the mains switch disconnector (SWIN) to completely turn off the CPS.
2) During battery mode operation with the timer not set, the CPS automatically switches off after 30 seconds. However,
if the timer is set, press and hold down the "STBY" key for at least 5 seconds to turn off the CPS. For complete
shutdown, open the mains switch disconnector (SWIN).
I
NTERNAL CLOCK SETTING
During the first installation, you must set the internal CPS clock through the configuration software. If the CPS remains off or
deactivated for more than 3 days, it will be necessary to re-configure the clock to avoid a failure of any programmed power-on
or shut-down configuration.
Summary of Contents for CSS SENTINEL TOWER CAM 3
Page 1: ......
Page 2: ......
Page 6: ... 4 ...
Page 8: ... 6 CPS VIEWS FRONT VIEW All models Display panel Removable front panel Ventilation grill ...
Page 39: ......
Page 40: ...0MNCAM3K0RUENUB ...