MASTER HE
SPTMHEE3T16FREN
26
13.
ENVIRONMENATL REQUIREMENTS
Ambient temperature for the UPS
0 ÷ 40° C
Maximum temperature for 8 hours a day
40° C
Average temperature for 24 hours
35° C
Recommended battery temperature
20 ÷ 30° C
Range of relative Humidity
30÷95% max (without condensing)
Maximum Operating Altitude
Up to 1000 m o.s.l.
(
derating of 1% each 100 m between 1000 and 4000 m)
Storage Temperature
From -25°C up to 60 °C (UPS)
-15, +40°C (for battery)
14.
TECHNICAL DATA
Mechanical Data
UPS Size (kVA)
100
120
160
200
250
Width (mm)
800
1000
Depth (mm)
850
Height (mm)
1900
Weight (Kg)
850
900
1015
1070
1300
Ventilation
Forced by internal fans
Level of cabinet protection
IP20 (higher levels of protection on request)
Input cables
From the bottom
Colour
RAL 7016