0MLMHTM16RUENUB page 83 / 85
33
Parallel Redund. lost: Redund.
unit OFF
In a parallel system, the redundancy is has been lost because the operating units
are less than t he set number of units.
34
Brake circuit fail
The optional brake circuit has a failure
35
Brake circuit Overload
The optional brake circuit has an overload
36
Rectifier switched OFF by
Remote command
The input converter stage is switched off by a remote command.
37
WAIT starting: NOT connect
the BATTERY
The input converter is starting, it needs to wait before connecting the battery
38
UPS SERVICE
The unit operation time exceeded the set time to require service.
39
BATTERY SERVICE
The battery operation time exceeded the set time to require service.
40
Battery charge < set level
[Ah%]
The system is waiting to start in normal operation, after a complete battery
discharging, because the battery is not charged above the requirement.
41
Input switch OFF
The external optional input switch is OFF.
42
INSULATION LOSS
A.C.
The external optional ac imput insulation checking device, detected the ac.
insulation lossing.
43
INSULATION LOSS
D.C.
The external optional dc output insulation checking device, detected the ac.
insulation lossing.
44
Motor Generator parallel mode
(rem.com)"
Optional operation
45
Overtemperature On Bypass
line transf.
Optional signal coming from an external transformer insert in the input bypass
line
46
Inverters OFF
The inverters are commanded to be OFF from an external command