Pag. 20 a 83
0MLMHTK65RUENUB
UPS 100-125kVA Power connection Terminals
Remove the jumpers present between the SWIN and SWBY.
Note: For the Input, Output and Battery connections, respect the order from the top to bottom, or right to left, as
described in the boxes. The label marked “N” present on the terminal identifies the neutral terminal. The neutral
input comes from the bypass source; no neutral is to be run from the rectifier input source, although the rectifier
source must be a grounded wye.
Bond: The UPS is provided with a separate bus bar that connects the Neutral Output to the frame Ground for delta
input connection. This is required to meet NEC grounding code for separately derived neutrals. When a Neutral is
provided in a Wye configured input connection the bus bar must be removed.
Once installation has been completed inside the equipment, replace the switch cover panel and close the door.
Bypass Input
A B C
Battery Input
+
-
Ground
Mains Input
C
B
A
Bond
Neutral Input
Load Output
C
B
A
N
Remove the
Bypass Jumpers