Pag. 23 a 83
0MLMHTK65RUENUB
External Over Current Protection device and terminals
CAUTION
to reduce the risk of fire, connect only to a circuit provided with branch circuit
protection with maximum current rating per the table, below, in accordance with the National
Electrical Code, ANSI/NFPA 70.
Input (for single input unit)
UPS models
Nominal Current
Maximum Current
OCP Current
OCP Device rating
Bolt Size (in.)
65 kVA
78.2A
89A
111.3A
125A
5/16
80 kVA
96.3A
109A
136.3A
150A
5/16
100 kVA
120.3A
136A
170A
175A
5/16
125 kVA
150.4A
160A
200A
200A
5/16
OCP= Over Current Protection Device, must be rated for branch circuit protection.
Rectifier Input (for dual input unit)
UPS models
Nominal Current
Maximum Current
OCP Current
OCP Device rating
Bolt Size (in)
65 kVA
78A
90A
112.5A
125A
5/16
80 kVA
94A
109A
136.3A
150A
5/16
100 kVA
118A
136A
170A
175A
5/16
125 kVA
147A
160A
200A
200A
5/16
Bypass Input (for dual input unit)
UPS models
Nominal Current
OCP Current
OCP Device rating
Bolt Size (in)
65 kVA
78.2A
97.8A
100A
5/16
80 kVA
96.3A
120.4A
125A
5/16
100 kVA
120A
150A
150A
5/16
125 kVA
150.4A
188A
200A
5/16
Output
UPS models
Nominal Current
Bolt Size (in)
65 kVA
78.2A
5/16
80 kVA
96.3A
5/16
100 kVA
120.3A
5/16
125 kVA
150.4A
5/16
CAUTION
Output circuit protection requirement is determined by distribution circuit. Smaller
wire may be used for load wiring if rated load current is not needed and the appropriate circuit
protection is applied. Output circuit protection must be provided as a part of the installation.