Pag. 72 a 83
0MLMHTK65RUENUB
1.1.33.15 IDENTIFICATION.
Press the following sequence of keys to access the menu: 3, 5, 436215, 7, 7:
Press key 1 to exit the menu. Keys 7 and 8 can be used to decrease or increase the number used for the identification
of a single unit in systems with several UPS connected to a single RS232 serial line. The basic number is 0 and
may be changed between values from 0 to 7.
1.1.33.16 STANDBY-ON
OPERATION
Press the following sequence of keys to access the menu: 3,5,436215,8:
Stby= 2sec. Stby_ON= 0
Adjustment: 4=Sma.ON, 5-,6+ 7=-,8=+
Press key 1 to exit the menu. Press key 8 Stby=1 to change the UPS from ON-LINE mode to STANDBY-ON mode.
Press key7 to change the UPS from STANDBY-ON mode to ON-LINE mode. The switch onto the bypass line may
be immediate when “Stby = 0 min.” or delayed by means of keys 5 and 6. The backup line must be available for the
time set within the acceptance field before the switchover can take place (see “PERSONALIZ. BYPASS
VOLTAGE FIELD” menu). The setting remains stored even during a shutdown due to a power failure. For a
description of the operation see the section “SETTING MODES”.
1.1.33.17
SMART ACTIVE OPERATION
Press the following sequence of keys to access the menu: 3,5,436215,8,4:
SMART ACTIVE S. Stby = 5 min. Stby_ON = 1
Adjustment: 4=Sma.OFF, 5-,6+ 7 = -, 8 = +
Press key 1 to exit the menu. When the Smart Active function is activated via key 4, Stby_ON goes to 1. The
setting remains stored even during a shutdown due to a power failure. There is a delay of 5 minutes before transfer
to SMART ACTIVE mode. For a description of the operation see the section “SETTING MODES”.
When the code is inserted the basic menu becomes:
NORMAL OPERATION SMART A.
P200, M OUT= 99%VA, BATT= 100%Ah, 5=ON
1.1.33.18 INVERTER-OFF/BYPASS
Press the following sequence of keys to access the menu: 3, 6 :
Exit the menu by pressing key 8 or any other key with a sequence other than the one described here. Pressing keys
4, 7, 2, 6, 3 in succession as shown on the display activates the command for bypass with shutdown of the inverter.
The command is executed after a few seconds’ delay to allow for cancellation. When this command is active, the
following alarm is shown on the display:
"
BYPASS COMMAND ACTIVE; 8=DEACTIV. ".
To return to normal operation, including after system shutdown, the command has to be cancelled by pressing key
8, or by sending the key code through the RS232.
NOTE To mask the command code 47263, insert code 436213 on the panel from the PERSONALIZATIONS menu
(keys 3, 5). Repeat the operation to display the code again.