page 34 / 84 0MLMHTM30RUENUA
5.5.6 SWOUT and SWMB EXTERNALS
See section “Parallel”.
5.6
Start-up procedure
mains power supply
The mains power supply has to be present in order to start up the UPS
The UPS output terminals will be powered in this phase and all loads connected will receive voltages. All
users must therefore be warned before carrying out the start-up procedure.
BATTERY CABINET if present:
The battery cabinet
must be
provided with a disconnect device for it to be connected to the UPS.
This disconnect device
must
be closed
only when
the UPS is started up regularly. During the UPS start-up
phase the disconnect device
must
remain in the open position.
Once the INPUT/OUTPUT and battery cables have been connected to the UPS terminals and before putting the switch
cover back in place, check that:
all the input/output terminals are securely tightened;
all the fuse holders have the fuse inserted, and are in the closed position;
the input and output ground conductor is connected correctly (yellow/green earth grounding cable);
check the polarity of the battery connections.
Replace the switch cover.
For the first start-up, the following operations should be carried out in this order:
1)
close input power switch SWIN,
2)
press button 1 twice, select the language and then press button 8 to return to the basic menu,
3)
after a few seconds, messages on the status of the UPS will start to be shown on the first line of the
display panel; these will include the following message relating to the battery disconnect:
Wait: DO NOT connect the BATTERY
4)
close the static static bypass line input switch SWBY,
5)
close the output switch SWOUT.
6)
do not close the external battery circuit breaker/disconnect device.
Once these operations have been carried out, the noise of the fans and the sound of the buzzer will be heard.
Close the external battery circuit breaker/disconnect
only when
the following message is no
longer shown
on the first line of the display panel
:
Wait: DO NOT connect the BATTERY
Note: If multiple battery cabinets are present, all breakers must be close within one minute after the
Wait: DO
NOT connect the BATTERY
message disappears. If this time constraint is a problem, do the following:
1.
Disable the automatic battery test by pressing button 3 then 5 on the control panel,
followed by entering the code 323232.
2.
Close all of the battery cabinet circuit breakers
3.
Re-enter the code 323232 to enable the battery test.
Configure the value of the battery capacity according to the instructions on page 53.
After the start-up operations have been completed, perform a manual battery test:
press button 3 and then 2 on the control panel. At the end of the test, after approx. 8 seconds, with the UPS
started correctly and with the battery connected on the signals and control panel, the two green input and
output LED’s must be lit continuously.