‐ 88 ‐
Storage temperature [°C]
-25/+60
Relative humidity [%]
5 - 95% (without condensation)
Installation maximum height
Up to 1000m above sea level
(power reduction 1% for every 100m between 1000m and 4000m)
Pollution degree
PD2
Vibration resistance
1 m/s
2
Overvoltage category /
Protection class
OVC II / class I
Power supply distribution
system
TT, TN,
IT (install a 4-pole circuit breaker on the power supply line)
Short circuit current
ICC=10kA at 415V maximum
Cable entry
Rear from the bottom MPX 130 PWC
Rear from the bottom or top MPX 100 CBC
Colour
RAL 9005
Standards
Safety: IEC EN62040-1 EMC: IEC EN 62040-2 Category C2
Mobile Cabinet
Castors (all cabinet types are sent without PM
3
and BU
4
)
1
Including redundancy
2
Applied conditions
3
PM = Power Module (referring to the 15 kW [MPX 15 PM] or 25 kW [MPX 25 PM] module)
4
BU = Battery Unit
NOTE: all performance quoted in a single row refer to any UPS system configuration from one to five modules operating in
parallel unless specified differently.
Summary of Contents for MPX 100 CBC
Page 1: ......
Page 2: ......
Page 8: ... 6 Top view Bottom view Display Wheels Bottom cable entry Fastening stands ...
Page 19: ... 17 A wring diagram of the Modular UPS Power Cabinet is provided below ...
Page 22: ... 20 The wiring diagram of the Modular UPS Combo Cabinet is provided below ...
Page 54: ... 52 Combo Cabinet MPX 100 CBC ...
Page 55: ... 53 Battery Cabinet MPW 170 BTC ...
Page 73: ... 71 MONITORING VIA WEB BROWSER ...
Page 91: ......
Page 92: ...0MNMPXK15RUENUB ...