- 9 -
PROFIBUS
I/O
DATA
The UPS’s values are presented to the Master PLC/Controller as easily processed I/O data.
INPUT DATA
REGISTER #
BYTE #
DESCRIPTION
UNIT
High
Low
1
1
2
States / alarms 1
2
3
4
States / alarms 2
3
5
6
Charge%
%
4 7
8
Autonomy
Minutes
5
9
10
RESERVED
6
11
12
Load phase L1
%
7
13
14
Load phase L2
%
8
15
16
Load phase L3
%
9
17
18
Input voltage (Ph-N) V1
V
10
19
20
Input voltage (Ph-N) V2
V
11
21
22
Input voltage (Ph-N) V3
V
12 23
24
Input
frequency
Hz/10
13
25
26
Output voltage (Ph-N) V1
V
14
27
28
Output voltage (Ph-N) V2
V
15
29
30
Output voltage (Ph-N) V3
V
16 31
32
Output
frequency
Hz/10
17
33
34
Output current phase L1
A/10
18
35
36
Output current phase L2
A/10
19
37
38
Output current phase L3
A/10
20
39
40
Output peak current phase L1
A/10
21
41
42
Output peak current phase L1
A/10
22
43
44
Output peak current phase L1
A/10
23
45
46
Battery current of positive bench
A/10
24
47
48
Battery current of negative bench
A/10
25
49
50
Battery voltage of positive bench
V/10
26
51
52
Battery voltage of negative bench
V/10
27
53
54
Output active power phase L1
kW/10
28
55
56
Output active power phase L2
kW/10
29
57
58
Output active power phase L3
kW/10
30
59
60
Output apparent power phase L1
kVA/10
31
61
62
Output apparent power phase L2
kVA/10
32
63
64
Output apparent power phase L3
kVA/10
33
65
66
Bypass voltage (Ph-N) V1
V
34
67
68
Bypass voltage (Ph-N) V2
V
35
69
70
Bypass voltage (Ph-N) V3
V
36 71
72
Bypass
frequency
Hz/10
37
73
74
System temperature
°C