TROUBLESHOOTING
Active controls:
indicate the presence of an active remote control.
CODE
DESCRIPTION
C01
Shutdown remote control
C02
Load on bypass remote control
C03
Startup remote control
C04
Battery test underway
LOCK
LOCK signals are usually preceded by an alarm signal and, due to their significance, cause the inverter to
shut down and the load to be powered via the bypass line (this procedure does not include locks from strong
and persistent overloads or locks due to short circuits).
CODE
DESCRIPTION
L03
Auxiliary power supply not correct
L04
Dissipators overtemperature
L05
Temperature sensor1 faulty
L06
Temperature sensor3 faulty
L07
Temperature sensor2 faulty
L10
Input fuse broken or input relay locked (does not close)
L13
Condenser precharge failed
L20
Condenser bank undervoltage
L21
Condenser bank overvoltage
L31
Bypass fault
L40
Inverter overvoltage
L41
Direct voltage in output
L42
Inverter voltage not correct
L43
Inverter undervoltage
L50
Overload: load > 103%
L51
Overload: load > 125%
L52
Overload: load > 150%
L53
Short circuit
Summary of Contents for SENTINEL DUAL SDL 10000
Page 1: ......
Page 2: ......
Page 4: ...4 ...
Page 14: ...14 ...
Page 15: ...15 I MANUALE D USO I ...
Page 50: ...50 ...
Page 51: ...51 GB USER MANUAL GB ...
Page 86: ...86 ...
Page 87: ...87 D BEDIENUNGSANLEITUNG D ...
Page 122: ...122 ...
Page 123: ...123 F MANUEL DE L UTILISATEUR F ...
Page 158: ...158 ...
Page 159: ...159 E MANUAL DE USO E ...
Page 194: ......
Page 195: ......
Page 196: ...0MNSDL6K5RU5LUC ...