BASIC MODELS
BBX SDL 240V BB NP A3
BBX SDL 240V BB NP A5
BATTERY
Nominal voltage
[Vdc]
240
End of charge voltage
[Vdc]
273
No. of batteries/V
20 / 12
SUNDRY
Ambient temperature (1)
[°C]
0 – 40
Humidity
< 90% non condensing
Protections
overcurrent - short circuit
Dimensions H x L x D
[mm]
455 x 175 x 660
Weight
[Kg]
63
65
(1) 20-25°C for extended battery life
T
ABLE OF OVERLOAD TIMES
OVERLOAD TIMES
OPERATION FROM
BYPASS
INVERTER
100% < Load 125%
Bypass active after 2 sec
Locked after 120 sec
Locked after 60 sec
125% < Load 150%
Bypass active after 2 sec
Locked after 4 sec
Locked after 4 sec
Load > 150%
Bypass active instantly
Locked after 1 sec
Locked after 0.5 sec