66
U
SE
Three phase version
1.
(8-10kVA THREE PHASE VERSION):
Use 3 cables with 6
mm
2
section (EARTH, L2 and L3) and 2 with 10 mm
2
section (N, L1) in input (N.B.: L1 and N have a greater
section because in operation from bypass they have to carry
all the input current)
.
For the output use 3 cables with 10
mm
2
section (EARTH, N and L).
With reference to the figure
shown at the side:
- Insert the cables from the 63A magneto-thermal switch into
seal stop P2 (input line).
- Insert the cables from the load into seal stop P1 (output line).
- Strip the cables observing the measurements provided.
- Insert the part that has just been stripped into the ferrules
provided.
(6,5kVA THREE PHASE VERSION):
Use 3 cables with 4
mm
2
section (EARTH, L2 and L3) and 2 with 6 mm
2
section
(N, L1) in input (N.B.: L1 and N have a greater section
because in operation from bypass they have to carry all the
input current)
.
For the output use 3 cables with 6 mm
2
section (EARTH, N and L).
With reference to the figure
shown at the side:
- Insert the cables from the 63A magneto-thermal switch into
seal stop P2 (input line).
- Insert the cables from the load into seal stop P1 (output line).
- Strip the cables observing the measurements provided.
- Insert the part that has just been stripped into the ferrules
provided.
2.
Connect the wires to the relative terminals strictly
following the instructions set out below:
Input line
a - Ensure that the magneto-thermal switch upstream
is open.
b - Connect the earth wire to terminal 5.
c - Connect the neutral wire to terminal 1.
d - Connect the phase wires to terminals 2, 3 and 4
(use the red wire for L1).
Output line
a - Connect the earth wire to terminal 6.
b - Connect the neutral wire to terminal 7.
c - Connect the phase wire to terminal 8.
Bypass line
a - Ensure that a jumper is connected at terminals 9
and 10; this is needed for the correct operation of
the UPS.
3.
Secure the cable guides to the flange, close the drawer and secure it with the screw removed previously.
Summary of Contents for SENTINEL DUAL SDL 10000
Page 1: ......
Page 2: ......
Page 4: ...4 ...
Page 14: ...14 ...
Page 15: ...15 I MANUALE D USO I ...
Page 50: ...50 ...
Page 51: ...51 GB USER MANUAL GB ...
Page 86: ...86 ...
Page 87: ...87 D BEDIENUNGSANLEITUNG D ...
Page 122: ...122 ...
Page 123: ...123 F MANUEL DE L UTILISATEUR F ...
Page 158: ...158 ...
Page 159: ...159 E MANUAL DE USO E ...
Page 194: ......
Page 195: ......
Page 196: ...0MNSDL6K5RU5LUC ...