75
U
SE
UPS
CONFIGURATION
The following table shows all the possible configurations available to adapt the UPS to the user’s
requirements.
KEY:
Indicates that the configuration can be changed from the display panel as well
as by means of the configuration software.
Indicates that the configuration can only be changed via the configuration
software.
FUNCTION
DESCRIPTION
PREDEFINED
POSSIBLE CONFIGURATIONS
MODE
Output frequency
To select the nominal
output frequency
Auto
50 Hz
60 Hz
Auto: automatic sensing from the input
frequency
Output voltage
To select the nominal
output voltage
230V
220V
230V
240V
220 ÷ 240 in 1V steps
(only via software)
Operating mode
To select one of the 4
different operating
modes
ON LINE
ON LINE
ECO
SMART ACTIVE
STAND-BY OFF
Start-up delay
Delay before
automatic restart after
the mains returns
5 sec.
Disabled
1 ÷ 255 in 1 sec. steps
Shutdown due to
minimum load
Automatic shutdown
of the UPS in
operation from the
battery if the load is
less than 5%
Disabled
Enabled
Disabled
Back up time
limit
Maximum time of
operation from the
battery
Disabled
Disabled (full battery discharge)
1 ÷ 65000 in 1 sec. steps
End of discharge
alert
Estimated remaining
back up time for the
end of discharge alert
3 min.
1 ÷ 255 in 1 min. steps
Battery test
Time interval for the
automatic battery test
40 hours
Disabled
1 ÷ 1000 in 1 hour steps
=
=
Summary of Contents for SENTINEL DUAL SDL 10000
Page 1: ......
Page 2: ......
Page 4: ...4 ...
Page 14: ...14 ...
Page 15: ...15 I MANUALE D USO I ...
Page 50: ...50 ...
Page 51: ...51 GB USER MANUAL GB ...
Page 86: ...86 ...
Page 87: ...87 D BEDIENUNGSANLEITUNG D ...
Page 122: ...122 ...
Page 123: ...123 F MANUEL DE L UTILISATEUR F ...
Page 158: ...158 ...
Page 159: ...159 E MANUAL DE USO E ...
Page 194: ......
Page 195: ......
Page 196: ...0MNSDL6K5RU5LUC ...