- 28 -
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
Bypass voltage
thresholds
Selects the permitted
voltage range for switching
to the bypass
Low: 180V
High: 264V
Low: 180 ÷ 200 in 1V steps
High: 250 ÷ 264 in 1V steps
Bypass voltage
Thresholds for
ECO
Selects the permitted
voltage range for operation
in ECO mode
Bassa: 200V
Alta: 253V
Low: 180 ÷ 220 in 1V steps
High: 240 ÷ 264 in 1V steps
Intervention
sensitivity for
ECO
Selects the intervention
sensitivity during operation
in ECO mode
Normal
Low
Normal
High
Power-on delay
Waiting time for automatic
switching back on after
mains power returns
5 sec.
Disabled
(1 ÷ 255) sec. in 1 sec. steps
Remote power-
on/off function
Select the feature
associated with the remote
control terminal board.
Pin 1-2 REPO
Pin 2-3 Remote
ON
Pin 1-2 REPO
Pin 2-3 Remote ON, Remote ON/OFF