TECHNICAL DATA
INPUT
Nominal voltage
[Vac]
220 - 230 - 240 (1W+N+PE)
Maximum operating voltage
[Vac]
300
Nominal frequency
[Hz]
50 - 60
Nominal current
(1)
[A]
18.5
BATTERY
Recharge time
[h]
< 4h for 80% of the load
Nominal voltage
[Vdc]
96
OUTPUT
Nominal voltage
(2)
[Vac]
Selectable: 220 /
230
/ 240
Frequency
(3)
[Hz]
Selectable: 50, 60 or
auto sensing
Rated apparent output power
[VA]
4000
Rated active output power
[W]
3600
Overload: 100% < load < 110%
Bypass line available:
- bypass activated after 2 secs
- locks after 120 secs
Bypass line NOT available:
locks after 60 secs
Overload: 110% < load < 150%
Bypass line available:
- bypass activated after 2 sec
- locks after 4 secs
Bypass line NOT available:
locks after 4 secs
Overload: load > 150%
Bypass line available:
- bypass immediately activated
- locks after 1 sec
Bypass line NOT available:
locks after 0.5 secs
OTHER
Leakage current to earth
[mA]
< 1.5
Ambient temperature
(4)
[°C]
0 – 40
Humidity
< 90% senza condensa
Protection devices
excessively low batteries - overcurrent - short circuit - overvoltage -
undervoltage - circuit breaker
Dimensions W x D x H
[mm]
131 x 640 x 448 - Tower
19” x 640 x 3U - Rack
Weight [Kg]
40
For more details please consult the web site.
(1)
@ nominal load, nominal voltage of 220 Vac, battery charging
(2)
To keep the output voltage within the indicated range of precision, recalibration may be necessary after a long period of
operation
(3)
If the mains frequency is within ±5% of the selected value, the UPS is synchronised with the mains. If the frequency is out
of the tolerance range or operating from the battery, the frequency is the one selected ±0.1%
(4)
20 - 25 °C for longer battery life
BATTERY BOX
KSDU096 – A - - - - - -
KSDU096 – L - - - - - -
KSDU096 – M - - - - - -
KSDU096 – V - - - - - -
Nominal battery voltage
[Vdc]
96
Dimensions W x D x H
[mm]
131 x 640 x 448 - Tower
19” x 640 x 3U - Rack
Weight [kg]
28
44
The “-” symbol replaces an alphanumeric code for internal use.