22
R.E.P.O.
The terminal block on the back of the UPS also implements the R.E.P.O. (Remote Emergency Power Off) function that
can be used to shut off the UPS remotely in case of an emergency.
The UPS is provided by the manufacturer with the REPO terminals short-circuited. For installation remove the short
circuit and connect to the device's normally closed contact
In case of an emergency, if the stop device is used, the REPO control is opened and the UPS goes into stand-by mode
and the load is completely disconnected.
Attention:
before restarting the UPS, reset the stop device.
The circuitry of the remote control terminal board is self-powered with SELV circuits. Therefore, an external voltage
supply is not required. When a contact is closed, a maximum current of 15mA circulates.
All connections with the remote control terminal board are made through a cable which guarantees a double insulation
connection.
If you would like to bring the R.E.P.O. control outside, unscrew the two screws securing the lower part of the backpack
and remove it (as indicated in the section “Connections”). Then, proceed as follows:
1.
Use a 2x0.75mm
2
cable to make the connection with the R.E.P.O. terminals.
2. Connect the two wires of the cable to terminals 7 and 8 (for version SPM 6), 9 and 10 (for versions SPH 8 - 10 - 10
ER - 15 - 20 - 20 ER) so as to be able to remotely shut off the UPS.
SPM 6
SPH 8 - 10 - 10 ER - 15 - 20 - 20 ER
3. Tighten the terminals well, close the back-pack and secure it with the screws taken out earlier.
Call Critical Power Supplies on 0800 978 8988 for the latest information