38
TECHNICAL DATA
UPS MODELS
SPM 6
SPH 8
SPH 10
SPH 10 ER
SPH 15
SPH 20
SPH 20 ER
INPUT
Nominal voltage
[Vac] 220 - 230 - 240
220 - 230 – 240 / 380 – 400 - 415
Maximum operating voltage
[Vac]
300
300 / 520
Nominal frequency
[Hz]
50 - 60
Nominal current
(1)
[A]
27
36 / 13
45 / 15
(46 / 19 ER)
67 / 23
89 / 30
(90 / 30,5 ER)
BATTERY
Recharge time (standard versions) [h]
< 4h for 80% of the load
Expandability and nominal
voltage of the Battery Box
180Vdc
240Vdc
240Vdc
240 +
240Vdc
240 + 240Vdc
Charging current
(for ER versions only)
Not applicable
8A
Not applicable
8A
8A
OUTPUT
Nominal voltage
(4)
[Vac]
Selectable:
220 /
230
/ 240
Selectable: 220 /
230
/ 240 – 380 /
400
/ 415
Frequency
(2)
[Hz]
Selectable: 50, 60 or
auto sensing
Nominal power
[VA]
6000
8000
10000
15000
20000
Nominal power
[W]
5400
6400
9000
13500
18000
Overload: 100% < load < 110%
Bypass line available:
activates the bypass after 2 seconds
locks after 120 seconds
Bypass line not available:
locks after 60 seconds
Overload: 110% < load < 150%
Bypass line available:
activates the bypass after 2 second
locks after 4 seconds
Bypass line not available:
locks after 4 seconds
Overload load > 150%
Bypass line available:
activates the bypass instantly
locks after 1 second
Bypass line not available:
locks after 0.5 seconds
OTHER
Leakage current to earth
[mA]
< 1,5mA
< 2mA
Ambient temperature
(3)
[°C]
0 – 40
Humidity
< 90% without condensation
Protection devices
excessively low batteries - overcurrent - short circuit - overvoltage -
undervoltage - circuit breaker
Dimensions W x D x H
[mm]
262 x 557 x 708
350 x 653 x
818
Weight
[kg]
62,4
77,7
84,1 (28,1 ER)
146
157 (48 ER)
Weight (for ER versions only)
[kg] Not applicable
Not
applicable
18
Not
applicable
25
Parallel
Max 2 units in parallel configuration with optional kit
For more details please consult the web site
(1)
at nominal load, nominal voltage of 230 Vac, battery charging
(2)
If the mains frequency is within ±5% of the selected value, the UPS is synchronised with the mains. If the frequency is
out of the tolerance range or operating from the battery, the frequency is the one selected ±0.1%
(3)
20 - 25 °C for longer battery life
(4)
To keep the output voltage within the indicated range of precision, recalibration may be necessary after a long period
of operation.
Call Critical Power Supplies on 0800 978 8988 for the latest information