TECHNICAL ASSISTANCE SERVICE
43
3
Boilers are calibrated in the factory for G20/G25 20/25
mbar.
If actual combustion parameter values differ from those
given in the tables below, contact
r
's Technical
Assistance Service.
Proceed as follows to set combustion parameters.
- Press and hold the
T
and
R
keys for between 3
and 6 seconds to enter chimney sweep mode. The 'chim-
ney sweep' symbol on the display starts to flash and the
display reads out the current boiler temperature.
- To set combustion parameters for maximum and mini-
mum power, press and hold the
T
and
R
keys
simultaneously for over 6 seconds. The boiler enters
fan speed control mode
- Press the
U
key.
The fan switches to maximum speed.
- Remove the top panel (1) of the boiler and insert the
combustion analysis probe into the socket (2) on the
flue gas vent fitting
- Set the CO
2
level by turning the adjuster screw (3) on
the fan group. Turn the screw clockwise to reduce CO
2
,
anti-clockwise to increase CO
2
.
Once the adjustments are complete, the combustion
parameters should be as specified in the tables below.
CO
2
values for functioning at
MAXIMUM POWER
3
1
2
CALIBRATING COMBUSTION PARAMETERS
TAU 55
UNIT
TAU 75
UNIT
TAU 110
UNIT
G20
9
8,9
9,1
G31
10,1
10
9,8
MAXIMUM POWER
TAU 110 UNIT
MAXIMUM POWER - TAU 55-75 UNIT