Combustion head settings indicated in the schedule are valid for most cases.
The setting of the fan output according to the installation should normally be done only through the air
damper. Should one subsequently want to retouch also the setting of the combustion head, with the
burner running, operate on the rod 

(1)

 with a 6 mm spanner 

(2)

 as follows:

Turn to the right: (sign 

+

), 

in order to increase the vol-

ume of air entering the combustion chamber and thus
diminishing its pressure.
There is a reduction of CO

2

 and the adhesion of the

flame to the air diffuser disc improves. 

(Setting advisable for ignitions at low temperatures).

Turn to the left:  (sign 

), 

in order to reduce the volume

of air entering the combustion chamber and thus increas-
ing its pressure. The CO

2

 improves and the adhesion of

the flame to the diffuser tends to reduce.

 (This setting is

not advisable for ignitions at low temperatures).

In any case do not bring the combustion head setting
more than one point away from that indicated in the
schedule. One set-point corresponds to 3 turns of the rod;
a hole 

(3)

 at its end facilitates counting the number of

turns.

 

AIR DAMPER ADJUSTMENT

The regulation of the air-rate is made by adjusting the
air damper 

(1)

, after loosing the screws 

(2)

When the optimal regulation is reached, 

screw tight

the screws (2).

 

The settings indicated in the schedule are purely indic-

ative. 
Each installation however, has its own unpredictable
working conditions: actual nozzle output; positive or
negative pressure in the combustion-chamber, the
need of excess air, etc. All these conditions may
require a different air-damper setting.

It is important to take account of the fact that the air
output of the fan differs according to whether the
burner has its metal cover fitted or not.  

Therefore we recommended to proceed as follows:
–  adjust the air damper as indicated in the schedule (page 5);

–  mount the cover, simply by means of the upper screw;

– check smoke number;

–  should it become necessary to modify the air output, remove the cover by loosening the screw,

adjust the air damper, remount the cover and finally recheck the smoke number.

1

2

3

6

D5551

1

2

D5231

4

Summary of Contents for 20013628

Page 1: ...20013748 3 01 2011 Installation use and maintenance instructions Light oil burner CODE MODEL TYPE 20013628 G5 LC 445T1 20035139 G5 LC 445T1 GB CN One stage operation...

Page 2: ...safety start up use and maintenance of the burner DELIVERY OF THE SYSTEM AND THE INSTRUCTION MAN UAL When the system is delivered it is important that The instruction manual is supplied to the user b...

Page 3: ...50 rpm 298 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 7 15 bar Absorbed electrical power 0 130 kW 1 Return line 2 Suction line 3 Gauge connection 4 Pump pressure regul...

Page 4: ...ge Burner It is necessary that the insulating gasket 9 fig 1 is placed between the boiler door and the burner flange This insulating gasket has six holes which if necessary can be modified as shown on...

Page 5: ...leakage of the valve PRIMING THE PUMP Start the burner and wait for the priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before repeating the operation A filte...

Page 6: ...neath the ignition transformer on a plug in support TESTING Check the shut down of the burner by opening the thermostats ATTENTION Do not connect burner s grounding to failure indicator terminal This...

Page 7: ...case of flame detachment during ignitions at low temper atures PUMP PRESSURE 12 bar the pump leaves the factory set at this value 14 bar improves flame retention it is therefore suitable for ignitions...

Page 8: ...one point away from that indicated in the schedule One set point corresponds to 3 turns of the rod a hole 3 at its end facilitates counting the number of turns AIR DAMPER ADJUSTMENT The regulation of...

Page 9: ...bustion head one set point further ahead than indicated in the instructions Example the instructions require to set the combustion head on set point 3 Instead the setting is made on set point 4 4 FAN...

Page 10: ...20013748 CN Technical Assistance Centre Assistance Centre Maintenance Contract...

Page 11: ...108 EC 73 23 EEC 2006 95 EC 98 37 EEC 92 42 EEC IP 40 EN 60529 445T1 28 60 kW 2 3 5 kg h 20 C 4 6 mm2 s 230V 10 50Hz 0 75A 2850 rpm 298 rad s 4 F 8 kV 16 mA 7 15 bar 0 13 kW 1 2 3 4 5 6 7 8 9 10 2 1 4...

Page 12: ...20013748 2 CN 0 8 0 0 4 mbar 2 3 4 5 kg h 25 30 60 kW D5226 35 40 45 50 55 0 2 0 6 2 3 272 107 236 130 37 4 5 89 233 11 180 D5554 180 75 72 150 4 5 9 1 6 D5242 2 2 D5572 S7384...

Page 13: ...Hg 20 H m L m I D 8 mm I D 10 mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 A A H m L m I D 8 mm I D 10 mm 0 0 5 1 1 5 2 3 3 5 35 30 25 20 15 8 6 100 100 100 90 70 30 20 H max 4 m H H max 4 m min 0 1 m D52...

Page 14: ...20013748 4 CN 50V T6A N L M S7026 1 mm2 A 230V 50Hz N L 230V 0 5A max 1 2 3 4 5 6 7 8 9 530SE T T 1 N 2 L 3 A 3 2 1 D5228...

Page 15: ...lavan W A E Steinen H Q Danfoss H 60 80 12 bar 12 bar 14 bar GPH bar kg h 4 0 60 60 80 11 2 3 1 5 2 0 65 60 80 12 2 6 2 2 2 0 75 60 12 3 0 2 5 2 5 0 85 60 12 3 4 3 3 1 00 60 12 4 0 4 4 5 1 10 60 12 4...

Page 16: ...20013748 6 CN 6 mm 2 1 CO2 CO2 1 3 3 2 1 2 5 1 2 3 6 D5551 1 2 D5231 4...

Page 17: ...7 20013748 CN 3 8 C 1 3 2 12 bar 8 C 14 bar 3 3 4 4 1 2 2 5 mm 4 0 3 mm D5230 A A 3 12s D5229 12s 5s...

Page 18: ......

Page 19: ......

Page 20: ...I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com Manufacturing site Riello Heating Equipment Shanghai CO LTD No 388 Jinbai Road Jinshan Industrial Zone 201506 Shang...

Reviews: