TECHNICAL ASSISTANCE SERVICE
49
ON
OFF
Regular maintenance may be a legal requirement. In Italy it is required by Presidential Decree 412 of the 26th August
1993. It is also essential for the safety, efficiency and durability of the boiler. Proper maintenance keeps consumption and
emissions down, and ensures that the boiler continues to operate reliably over time.
Perform the following operations before beginning any
maintenance.
- Switch the electricity supply OFF at the system’s main
switch and at the control panel.
- Close the fuel shut-off cocks.
Once all the necessary maintenance has been completed, restore all original settings (see the values in the tables below).
Calibration table for STANDARD NOZZLE
Description
TAU UNIT
OIL 35 B
OIL 55 B
Air damper position
4
5
line
Standard nozzle
0,75
1,1
GPH
80° HF
80° HF
Delavan
mark
Head adjustment
Fixed
Fixed
line
Pump pressure
14,0
14,5
bar
Fuel flow rate
2,95 (± 4%)
4,6 (± 4%)
kg/h
Maintenance