POWER SUPPLY FREQUENCY ERROR
The burner controller automatically detects the frequency of the main power supply over the interval of 50 to 60 Hz.
Operating times are verified for both frequencies.
An error is indicated by the LED flashing.
- If the fault is detected before the heat request or during pre-heating, the burner does not start and the fault is appro-
priately signalled.
- If the fault is detected during the pre-purging, the burner remains in purge condition and the fault is appropriately sig-
nalled.
- If an error is detected during normal functioning, the burner continues to function normally.
FAN MOTOR CONTROL
The burner controller automatically monitors the functioning of the fan motor and enters lockout in the event of a fan
motor failure.
FUEL OIL VALVE CONTROL
The burner controller automatically detects the presence of the fuel oil valve solenoid and enters lockout in the event of
a fuel oil valve solenoid failure.
The fault is indicated by the blinking LED.
- if the anomaly is detected during the initialisation, the burner goes into lockout.
- if the anomaly is detected during the pre-purging, the burner goes into lockout.
- During a recycling, if the fault is detected, the burner does not start and goes into lockout.
- The fault is not detected during normal operation, the burner remains in this state.
- The fault is not detected if the burner is in lockout.
INTERNAL VOLTAGE ERROR
The burner controller automatically checks that internal voltage is correct. An error is indicated by the LED flashing.
- If the fault is detected during the initialisation, the burner does not start.
- If an error is detected after a lockout, the burner will not start up.
- If an error is detected after a shutdown test, the burner will not start up.
- If the fault is detected during normal operation, the burner remains in this state.
The burner starts up as soon as the error disappears.
REMOTE RESET / RESET BUTTON FAULT
In any state (thermostat ON/OFF), if the reset button is faulty or is kept pressed for more than 60 seconds, the fault is
indicated by the blinking of the LED, as long as it is present.
- This fault is only displayed and the LED stops blinking when the fault disappears.
- If the fault is detected during pre-purging, pre-heating or safety time, the burner does not stop and the start-up
sequence continues.
- If the fault is detected during operation, the burner does not stop.
- If the fault is detected during a lockout, the fault is not signalled and the burner cannot be reset.
EEPROM CONTROL
The burner controller automatically checks for errors in the microcontroller EEPROM and enters lockout if an error is
detected.
An error is indicated by the LED flashing.