TECHNICAL ASSISTANCE SERVICE
61
PROGRAMMING MENU
The programming menu can be accessed via the integrated reset button, or by remote reset during OPERATION and
in STAND-BY.
If in page menu the reset or remote reset button is not pressed within 10 seconds the page will be automatically exited
and there will be a green LED blinking for the time set.
If the number of presses on the reset or remote reset button exceeds the maximum allowable, the value that stays in
memory will be the maximum one.
If the reset or remote reset button is pressed for more than 60 seconds, a button error will be displayed.
Block diagram for entering the menu
NORMAL FUNCTIONING (FLAME LIT) AND STANDBY
SHUTDOWN TEST
POST-PURGING
2 RED
1 GREEN
3 GREEN
AUTOMATIC
EXIT
10 SECS.
AFTER RELEASE
10 SECS.
AFTER RELEASE
10 SECS.
AFTER RELEASE
20 SECS.
LAST LOCKOUT
IN MEMORY
25 SECS.
4 GREEN
5 SECS.
10 SECS.
BURNER STATE
EXIT
TYPE OF
FUNCTION
BUTTON
RELEASE
TIME
NUMBER OF
FLASHES
CONTROLLED
SHUTDOWN
AND RESTART
Function
Button re-
lease time
No . of blinks
of the LED for
menu page
No . of times the reset
button is pressed
No . of blinks of the
LED (green)
Quitting the menu
Switching off test 5s ≤ t < 10s
2 blinks
RED
/ none
/ none
Automatic starting
at the end of the
blinking
Post-purging
10s ≤ t < 15s 1 blink
GREEN
1 = 10 sec.
2 = 20 sec.
3 = 30 sec.
4 = 60 sec. (default)
5 = 120 sec.
6 = 0 sec. (disabled)
1 blink
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
10 sec. after button
release
Intermittent oper-
ation
20s ≤ t < 25s 3 blinks
GREEN
1 = 0 disabled
2 = 1 hour
3 = 24 hours (default)
1 blink
2 blinks
3 blinks
10 sec. after button
release
Last lockout
saved
25s ≤ t < 30s 4 blinks
GREEN
/ none
Displaying the type
of lockout according
to table
on page 57
10 sec. after button
release
Switching off test
Sequence for shut-down test programming:
- Programming allowed in OPERATING mode and in STAND-BY.
- Press the button for 5 sec.
≤
t < 10 sec.
- The RED LED blinks twice (0.2 sec. ON; 0.2 sec. OFF).
- Release the button.
- The burner will begin a shut-down, followed by a restart.
After shut-down, the burner restarts automatically and the no. of recycling attempts is restored.
At the exit of shut-down test page menu there are no blinking led.