12
DEFAULT PARAMETER SETTINGS TABLE
Relay 3 and Cascade activation
Menu
Description
Setting range
Default
User setting
6.7
Relay 3
ENTER (confirm)
6.7.3
Relay 3
ENTER (confirm)
6.7.3.1
Relay 3
ON/OFF
OFF
ON
6.7.7
Cascade
ENTER (confirm)
6.7.7.1
Cascade
ON/OFF
OFF
ON
Confirm with (YES) and exit.
Enter the cascade settings into control unit
Menu
Description
Setting range
Default
User setting
4.7
Cascade system
4.7.1
2-way cold water valve
On - not present /
Off - present
Off
4.7.2
Startup % flow on
min 30% max 99%
50%
4.7.3
Shut-down % flow off
min 10% max 90%
25%
4.7.4
On/Off delay
1-10 seconds
6 secs.
Enter the recirculation parameters only in the control unit in which the recirculation kit is installed.
Enter the settings in the order given in the following table:
Menu
Description
Setting range
Default
User setting
6.
Special functions
6.6
Relay 2
6.6.1
Recirculation
On/Off
Off
6.8
V2 signal
6.8.1
Recirculation
On/Off
On
6.3
Pump V2
6.3.1
Pump type
0-10V / PWM
PWM
6.3.2
Pump
Solar / Central heating /
Profile 1-11 / Manual
Solar
6.3.3
Output signal
Normal / inverted
Normal
6.3.4
PWM off
0-13%
2%
6.3.5
PWM on
2-50%
13%
6.3.6
PWM Max
50-100%
93%
6.4
Speed control, pump V2
6.4.1
Speed control, pump V2
On/Off
On
6.4.2
Max. pump speed
70-100%
100%
6.4.3
Min. pump speed
10-95%
10%
6.6
Relay 2
6.6.6.1
Always on
On/Off
On
b
Repeat the same operation for all the control units.