2044
1
GB
Forced draught gas burners
GS5
COD.
3755213 – 3755214
TYPE
552T1
TECHNICAL FEATURES
For gas family 3 (LPG) ask for separate kit.
◆
The burner meets protection level of IP 40, EN 60529.
◆
CE marking according to Gas Appliance Directive 90/396/EEC; PIN 0063AP6680.
◆
According to directives: EMC 89/336/EEC, Low Voltage 73/23/EEC, Machines 89/392/EEC and
Efficiency 92/42/EEC.
◆
Gas train according to EN 676.
NOTE
The cable gland (5) and the screw for fixing the cover (6) supplied with the burner, must be fitted to
the same side of the gas train.
Thermal output
18 – 58 kW
–
15,500 – 50,000 kcal/h
Gas
(Family 2)
Net heat value
8 – 12 kWh/m
3
–
7,000 – 10,340 kcal/m
3
Pressure
min. 20 mbar
–
max. 35 mbar
Electrical supply
single phase,
230 V
±
10%
~
50Hz
Motor
230 V / 0.65 A
Capacitor
2
m
F
Ignition transformer
primary 230 V / 0.2 A
–
secondary 8 kV
Absorbed electrical power
0.11 kW
COUNTRY
DE
DK - AT - GR - SE
GB - IE
LU
GAS CATEGORY
II2ELL3B/P
II2H3B/P
II2H3P
II2E3B/P
1 – Air-dampers
2 – Screws for fixing the air-damper
3 – 6 pole gas-train plug
4 – 7 pole electrical controls plug and
socket
5 – Cable gland
6 – Screw for fixing the cover
7 – Lock-out lamp and reset button
1
5
2
6
7
D5134
Fig. 1
2
4
3