background image

20146103

26 

GB

Installation

5.13.9 Duration of ignition transformer discharge

The spark ignition is present during all safety time.

5.13.10 Reset by button and remotely of the burner

The burner can be released by pressing, for at least 0.4 seconds,
the reset button integrated in the control box and the unlocking
occurs only when the button is released.
The burner can also be reset using an external button (remote re-
set) connected to the R terminals (see RS electric diagram) on
the burner pressing for at least 0.8 seconds.

5.13.11 Protection reset

The burner can be reset only 5 times consecutively, then power
supply has to be disconnected for a new 5 reset possibilities. 
The burner can only be reset if power supply is applied to the con-
trol box.

5.13.12 Reset push-button anomaly

If the reset button is faulty or is kept pressed for more than 60
seconds, the fault is indicated by the blinking of the LED (see par-
agraph 

“Fault diagnostics - lockouts”

 on page 24) as long as

it is present.
This fault is merely a visualisation.

If the fault is detected during pre-purging or safety time, the
burner does not stop (the start-up sequence will continue).

If  the  fault  is  detected  during  operation,  the  burner  does
stops and stays stopped with the fault signal active.

If the fault is detected during a lockout, the fault is not sig-
nalled and the burner cannot be reset.
When the fault disappears, the LED stops blinking.

5.13.13 External lockout signal (S3)

The burner is equipped with an external locking signal function,
i.e. to signal (together with the integrated reset button) a burner
locking alarm. 
The control box provides a command of an external lamp using 
the S3 output (230Vac-0.5Amp max).

5.13.14 Hour counter functioning (B4)

The burner has an hour counter function that is active as long as
the 1st stage oil valve is open and therefore as long as fuel is be-
ing consumed. 
The  control  box  provides  an  external  meter  through  the
Hour_Counter output (230V AC-0.1Amp max.) of the control box
connected to pin B4.

5.13.15 Monitoring the power supply voltage

The control box automatically measures the mains voltage. 
If the voltage is less than 160V or more than 280V, the burner
stops, interrupts the operating cycle and remains in stand-by, sig-
nalling a fault. The fault is indicated by way of the blinking LED
(see paragraph 

“Fault diagnostics - lockouts”

 on page 24). 

The burner restarts when the voltage is exceeds approx. 170V or
is brought back under 270V.

If the fault is detected with flame operation, the valve is imme-
diately closed and the motor stops.

If  the  anomaly  is  detected  during  pre-purging,  the  motor
stops.

If when the main power supply switch is closed or after there
has been no power, the mains voltage stays within the inter-
mediate values (160-170V or 270-280V) the burner does not
start.

If the burner is in lockout, the mains voltage is monitored but
is not signalled in that there is a lockout signal.

During the ignition time the mains voltage monitoring is deactivat-
ed.

5.13.16 Frequency supply error

The control box automatically detects the value of the frequency
of the main supply in the range of 50 - 60 Hz, in both cases work-
ing times are verified. The fault is indicated by way of the blinking
LED  (see  paragraph 

“Fault  diagnostics  -  lockouts”

  on

page 24). 

If  the  anomaly  is  detected  before  heat  demand  the  burner
does not start.

If  the  fault  is  detected  during  the  pre-purging,  the  burner
remains in purge condition and the fault is appropriately sig-
nalled.

The fault is not detected during normal running, the burner
remains in this state.
When the fault disappears, the burner restarts.

5.13.17 Internal voltage anomaly

The control box automatically detects if the internal voltage works
correctly. The fault is indicated by way of the blinking LED (see
paragraph 

“Fault diagnostics - lockouts”

 on page 24). 

If the anomaly is detected during the initialisation check time,
the burner does not start.

If the anomaly is detected after a lockout the burner does not
start.

If the anomaly is detected after a shut-down test, the burner
does not start.

The fault is not detected during normal running, the burner
remains in this state.
When the fault disappears, the burner restarts.

5.13.18 Checking the fan motor

The control box automatically detects the presence of the fan mo-
tor and, in the event of a fault, it performs a lockout. The lockout
is indicated by the blinking of the LED (see paragraph 

“Fault di-

agnostics - lockouts”

 on page 24).

WARNING

In  the  event  of  continuous  recycling  or  heat  re-
quests that are close together, the maximum al-
lowed number of cycle repetitions for the ignition
transformer is one every minute.

WARNING

If the reset button is pressed for more than 2 sec-
onds, the control box goes into visual diagnostic
mode and the indicator LED begins to blink (see 
‘Fault diagnostics - lockouts” a pag. 24).

Summary of Contents for 40 FS5D

Page 1: ...Installation use and maintenance instructions 20146103 2 09 2018 Forced draught gas burner Two stage operation CODE MODEL TYPE 3758705 RIELLO 40 FS5D 587M GB...

Page 2: ...Translation of the original instructions...

Page 3: ...minary checks 14 5 4 1 Control of the supply 14 5 4 2 Control of burner characteristics 14 5 5 Operating position 14 5 6 Securing the burner to the boiler 15 5 6 1 Hinge installation 15 5 7 Positionin...

Page 4: ...e menu 29 5 14 3 Shut down test 30 5 14 4 Post purging and continuous purging 30 5 14 5 Intermittent operation 30 5 14 6 Setting the opening delay of the 2nd stage 30 5 14 7 Setting a long pre purging...

Page 5: ...and according to the European Directives GAR 2016 426 EU Gas Appliances Regulation MD 2006 42 EC Machine Directive LVD 2014 35 EU Low Voltage Directive EMC 2014 30 EU Electromagnetic Compatibility Suc...

Page 6: ...ed out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wit...

Page 7: ...vent of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreas...

Page 8: ...intenance Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the speci...

Page 9: ...Fuel Natural gas Light oil LPG Variations Electrical supply of the system 1 230 50 1 230 60 F S 5 1 230 50 BASIC DESIGNATION EXTENDED DESIGNATION 1 230V 50Hz 1 230V 60Hz Light oil Natural gas K Conic...

Page 10: ...are given in Fig 1 Model RIELLO 40 FS5D Type 587 M Heat output Hi 1 min max kW kcal h 12 23 58 10 000 20 000 50 000 Fuel Family 2 NCV 8 12 kWh m3 7 000 10 340 kcal m3 Pressure min 8 mbar max 200 mbar...

Page 11: ...the manufacturers 4 7 Correlation between gas pressure and burner output To obtain the maximum output Fig 3 it is necessary to have 4 6 mbar measured on the pipe coupling with the combustion cham ber...

Page 12: ...Electrode probe 16 Air damper opening motor 17 4 pole socket for 2nd stage 4 9 Burner equipment Screws with nuts No 4 Insulating gasket No 1 Cover fixing screw No 3 Cable grommet No 1 Hinge No 1 7 pi...

Page 13: ...the control box from the burner it is necessary to Fig 5 disconnect all the connectors connected to it all the plugs the high voltage cables and the earth wire TB unscrew the screw A and pull the cont...

Page 14: ...anner and correctly fix the cover Check the wiring is in order Falls and collisions can negatively affect the safety func tions In this case the servomotor must not be operated even if it displays no...

Page 15: ...r If the smoke pipe is closed the burner must be drawn back till the extraction of blast tube from the furnace Before oper ating in this way take the voltage off 5 3 Handling The transport weight is g...

Page 16: ...must not be abandoned as they are potential sources of danger and pollution they should be collected and disposed of in the appro priate places WARNING A burner label that has been tampered with re m...

Page 17: ...ner WARNING Boiler door must have a max thickness of 80 mm refractory lining included If the thickness is great er max 105 mm a combustion head extension should be used to be requested separately S739...

Page 18: ...st proceed as follows Take the burner to the 2nd stage The mobile air damper 1 Fig 14 activated by the motor 2 ensures the suction inlet opens completely Adjust 2nd stage air delivery using the fixed...

Page 19: ...EN 676 and provided separately from the burner Supplied separately for its adjustment see the enclosed instructions The train burner combination is indicated in Tab F Tab F Explosion danger due to fue...

Page 20: ...ig 4 on page 10 of the burner DANGER Disconnect the electrical power using the main switch Check that there are no gas leaks Pay attention when handling the train danger of crushing of limbs Make sure...

Page 21: ...on a cycle arrest must be ensured within 24 hours with the use of a time switch positioned in series with the thermostatic line Refer to the wiring diagrams The electrical safety of the device is obta...

Page 22: ...electrical supply of the burner corresponds to that shown on the identifica tion label and in this manual The section of the conductors must be at least 1mm2 Unless requested otherwise by local standa...

Page 23: ...1st stage hour counter h2 2nd stage hour counter PG Min gas pressure switch S3 Remote lock out signal 230V 0 5A max T6A Fuse TL Limit thermostat TR 2nd stage thermostat TS Safety thermostat VPS Valve...

Page 24: ...5 Delay time between the 1st and 2nd stage ts Safety time V1 1st stage valve V2 Valve 2nd stage t2 t1 t3 t4i ts HT FM ID V1 LED P M LED t4l PG P TR P M AD t5 V2 SO SO POWER SUPPLY Signal not requested...

Page 25: ...5 t3r A recycle attempt is made if there is an air pressure drop during the pre purging stage there is then a lockout in the event of a second loss of air pressure between the 16th second and the 29th...

Page 26: ...s flame loss during operation RED fast blinking 0 2 0 2 Lockout due to a drop in air pressure after the pre purging was repeated due to a previous lack of air or 10 sec before the end of the pre purgi...

Page 27: ...the flame goes out and the start up sequence restarts If the switch off test is enabled the number of repetitions of the start up sequence see paragraph Recycle and limit of repeti tions on page 25 an...

Page 28: ...paragraph Fault diagnostics lockouts on page 24 The burner restarts when the voltage is exceeds approx 170V or is brought back under 270V If the fault is detected with flame operation the valve is im...

Page 29: ...t for a pre set time The burner switches off the flame when the heat request thermostat opens cutting off the fuel sup ply to the valves The post purging function is not performed after a lockout of t...

Page 30: ...with the operating hours also the number of the burner s first stage valve openings is saved In the menu see paragraph Programming menu on page 29 it is possible to independently reset both the opera...

Page 31: ...the menu Switching off test 5s t 10s 2 blinks RED none none Automatic at the end of the blink Post purging Continuous purging 10s t 15s 1 GREEN blink 1 1 minute 2 2 minutes 3 3 minutes 4 4 minutes 5 5...

Page 32: ...e button GREEN led OFF Press the button 1 time to enable a shut down every hour Press the button 2 times to enable a shut down every 24 hours GREEN led ON and OFF every time press and release After 10...

Page 33: ...setting the programming menu parameters and the lockout log The control box allows you to reset the log and the number of lockouts the operating hours the number of ignitions and recov er the menu s d...

Page 34: ...st or af ter a recycle due to flame loss during operation After 15 seconds the air pressure is too low the head has been poorly adjusted The air pressure switch is defective change it Lockout for loss...

Page 35: ...the knob anticlockwise to an extent that is around 20 of the adjusted value and then check that the burner starts up properly If the burner locks out again turn the knob slightly in an anticlock wise...

Page 36: ...ls or close open position indicator that turn on at the same time as their power supply 7 2 3 Checking and cleaning Combustion Check there are no occlusions or obstructions in the fuel supply or retur...

Page 37: ...P The specified life cycles do not refer to the warranty terms indicated in the delivery or payment conditions Tab P 7 3 Opening the burner If maintenance of the combustion head is required refer to t...

Page 38: ...Adjust them The connections in the control box are wrongly inserted Check and connect completely all the plugs The air pressure switch is changed over to the operational position Replace the pressure...

Page 39: ...mmedi ately and the motor stops The pressure then starts to increase again the pressure switch closes the start up cycle be gins again and so on Lower and set the pressure switch Faults Possible Cause...

Page 40: ...g kit Gas trains in compliance with EN 676 Please refer to manual A Appendix Accessories Burner Standard length mm Long head length mm Code RIELLO 40 FS5D 100 125 3000820 Burner Projection mm Code RIE...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Reviews: