2916293
2
GB
LPG kit
2.1
Kit description
The kit allows the burners type 876T, 878T, 874T, 886T, 883T,
888T, 877T, 879T, 875T, 873T, 884T and 889T designed to
work with natural gas to burn LPG and butane and is composed
of:
2.2
Technical features
2.3
Conversion
On the natural gas head, substitute the distributor unit 1) with the
one supplied. If the head features a central air pipe and an adjust-
ment ring nut 2), before fitting the distribution unit 1), remove the
entire assembly 2) and close the rear hole on the head using the
disc and screws supplied as standard equipment 3).
Reassemble the electrode and probe, adjusting them as shown
in Fig. 1 and Fig. 2
2
LPG kit
Description
Quantity
Distributor assembly
1
Sealing disk
1
Screws
2
Label
1
Instruction
1
WARNING
Apply the self-adhesive label for LPG operation
near the characteristics label.
Before starting the kit installation operations, get a
suitable lifting system ready.
Be careful as some drops of fuel may leak out dur-
ing the kit installation phase.
Burner type
876T - 878T
877T - 879T
874T - 886T
883T - 888T
875T - 873T
884T - 889T
Model
RS 25/M - 25/E BLU
RS 35/M - 35/E BLU
RS 34/M - 34/1 MZ
RS 34 - 34/E MZ
RS 44/M - 44/1 MZ
RS 44 - 44/E MZ
Burner output
45 ÷ 370 kW
39 ÷ 320 Mcal/h
72 ÷ 480 kW
62 ÷ 413 Mcal/h
70 ÷ 390 kW
60 ÷ 336 Mcal/h
100 ÷ 550 kW
86 ÷ 473 Mcal/h
Minimum gas pressure
Maximum capacity requires:
25.8 mbar
23.3 mbar
28 mbar
34.3 mbar
measured on the pipe coupling, with 0 mbar resistance in the combustion chamber and gas with net cal-
orific value of 22.200 kcal/Nm
3
Fuel
Commercial LPG (C
3
H
8
= 93 - 94%)
Net calorific value = 25.8 kWh/Nm
3
- 22.200 kcal/Nm
3
DANGER
Disconnect the electrical supply from the burner
by means of the main system switch.
Fig. 1
20080838