25
20013962
GB
Maintenance
9.5.2
Continuous purging function, (only for
applications in which this is provided for)
Continuous purging is an operation that maintains the air purging
regardless of whether there is a request for the burner to turn on
or not. From the moment it is set, the motor keeps running wheth-
er the limit thermostat (
TL
) has not been switched (burner off), or
when the burner is blocked.
Only when the limit thermostat (
TL
) is switched does the motor
stop for the standby time of four seconds (standby position = t2 +
t1).
The function can be set from the reset button when the limit ther-
mostat (
TL
) is not switched (burner off), by following the proce-
dure in the post-purging function paragraph 9.5.1 "Post-purging
function (t6)" by pressing the button
7 times = continuous purg-
ing
.
To reset this
function, press and hold the button for at least 5 sec-
onds at least, till the LED indicator changes to red then release it
without carrying out any operation, then wait for 20 seconds for the
burner to start again.
If when the limit thermostat (
TL
) switches, there is an extraneous
light the motor stops as long as the extraneous light is there fol-
lowed by the block.
The control box’s factory settings are as follows:
0 minutes = no
continuous post-purging
.
9.5.3
Long pre-purging (t7)
operation
The long pre-purging makes it possible too lengthen the purging
of the air by the switching of the limit thermostat (
TL
) on the igni-
tion of the flame for up to two minutes.
The function can be set from the reset button when the limit ther-
mostat (
TL
) is not switched (burner off), by following the proce-
dure in the post-purging function paragraph 9.5.1 "Post-purging
function (t6)" by pressing the button
8 times = long pre-purging
.
To reset this
function, press and hold the button for at least 5
seconds at least, till the LED indicator changes to red then re-
lease it without carrying out any operation, then wait for 20 sec-
onds for the burner to start again.
The control box’s factory settings are as follows:
0 minutes = no
long pre-purging
.
9.5.4
Function setting procedure using reset button
Control box function
Actions on the reset button
Possible
reset button use status
Reset
1 to 2 seconds
After control box lockout
Visual diagnostics of lockout
causes
3 seconds
After control box lockout
Post-purging
5 seconds then press
once = 1 minute
With limit thermostat (
TL
) not switched
(burner off)
Continuous purging
(only for applications provided for).
5 seconds then press
7 times = continuous purging
With limit thermostat (
TL
) not switched
(burner off)
Long pre-purging
5 seconds then press
8 times = long pre-purging
With limit thermostat (
TL
) not switched
(burner off)
Resetting
set functions
5 seconds
With limit thermostat (
TL
) not switched
(burner off)
Resetting operating parameters
5 seconds
With limit thermostat (
TL
) switched during pre-purging