20094575
32
GB
Start-up, calibration and operation of the burner
5.6
Final checks (with the burner working)
Tab. F
Open the control limit operation
Open the high limit operation
The burner must stop
Rotate the maximum gas pressure switch knob to the
minimum end-of-scale position
Rotate the air pressure switch knob to the maximum end
of scale position
The burner must stop in lockout
Switch off the burner and disconnect the voltage
Disconnect the minimum gas pressure switch
The burner must not start
Cover the flame sensor
The burner must stop in lockout due to firing failure
WARNING
Make sure that the mechanical locking systems on
the different adjustment devices are fully tightened.