Installation
17
20026767
4.5
Blast tube length
The length of the blast tube must be selected according to the indi-
cations provided by the manufacturer of the boiler, and it must be
greater than the thickness of the boiler door complete with its insu-
lation.
The range of lengths available, L (inch), is as follows:
For boilers with front flue passes 6) or flame inversion cham-
bers, protective insulation 4) must be inserted between the
boiler refractory 5) and the blast tube 3).
This protective insulation must not compromise the extraction
of the blast tube.
For boilers having a water-cooled front the insulation 4)-5)
(Fig. 11) is not required unless it is required by the boiler man-
ufacturer.
4.6
Securing the burner to the boiler
Secure the flange 2)(Fig. 11) to the boiler plate, inserting the
gasket 1)(Fig. 11).
Use the 4 screws, after first protecting the thread with an anti-
locking product.
The seal between burner and boiler must be airtight.
4.7
Ignition pilot adjustment
Place the pilot and electrode as shown in Fig. 12.
The pilot works correctly at pressures ranging from 5 - 12” WC.
Model
L
(short blast tube)
L
(long blast tube)
RS 45/E LN
9
1
/
32
“
13
15
/
16
“
3
6
5
4
6
1
2
L
Fig. 11
D10436
5/ 16"
1/ 8"
Fig. 12
D10437