5
Condexa Pro
BOILER MODELS
CONDEXA
PRO 50 P
CONDEXA
PRO 70 P
Condexa
PRO 100 P
MAXIMUM THERMAL POWER
Useful (80/60°C)
kW
44,2
67
95,2
Useful (50/30°C)
kW
48,8
73,9
105,1
Furnace
kW
45,0
68
97
MINIMUM THERMAL POWER
Useful (80/60°C)
kW
8,9
13,5
19,2
Useful (50/30°C)
kW
9,9
14,9
21,1
Furnace
kW
9,0
14
19,4
EFFICIENCY
Useful (80/60°C)
%
98,34-
98,9
98,1-98,9 98,1-98,8
Useful (50/30°C)
%
108,6-119,7 108,1-109,3 108,2-109,2
With reduced load 30% (return 30°C)
%
109,2
109
109
COMBUSTION
Chimney and blanket losses with
burner on
%
2,3-1,1
2,3-0,9
2,6-0,9
Chimney losses with burner off
%
0,1
0,1
0,1
Flue flow rate
kg / s
0,020
0,03
0,046
GAS EMISSION VALUES AT MAX AND MIN FLOW RATES G20 (**)
MAXIMUM
CO s.a. less than (***)
ppm
73
90
92
CO
2
%
9
9
9
NOx (EN 677) (***)
ppm
30
30
30
Flue temperature
°C
67,5
72
78
D
T flue - return water
K
7,50
12
18
MINIMUM
CO s.a. less than (***)
ppm
2,3
6,5
7,5
CO
2
%
9
9
9
NOx (EN 677) (***)
ppm
30
30
30
Flue temperature
°C
61
61
62
D
T flue - return water
K
1
1
2
NOx class
6
6
6
Electric power: circulator, total
105
77
203
(**) Verification carried out with concentric pipe Ø 60-100 mm length 0.85 m; water temperatures 80-60 °C.
(***) Graphs for intermediate power values are also available. The expressed data must not be used to certify the plant; for certification the data
indicated in the "installation manual" measured at the time of the first ignition must be used.
LAW TABLE 10