49
I
NSTALLATION AND
U
SE
Table 2
Battery LED bar
Battery level
1
2
3
4
5
0%~20%
●
20%~40%
●
●
40%~60%
●
●
●
60%~80%
●
●
●
●
80%~100%
●
●
●
●
●
Table 3
Battery LED bar
Input Voltage
1
2
3
4
5
190V~200V
●
200V~230V
●
●
230V~250V
●
●
●
250V~260V
●
●
●
●
>260V
●
●
●
●
●
Tab. 4
Load LED bar
Load level
25
50
75
100
!
0~5%
5~25%
●
25%~50%
●
●
50%~75%
●
●
●
75%~102%
●
●
●
●
>102%
●
●
●
●
●
●
LED on with steady light
♦
LED with flashing light on (1 flash per second)
O
VERLOADS ON THE
UPS
The following table shows how the UPS reacts when mains and battery overloads occur and indicates the time
that the UPS will remain powered.
OVERLOAD LEVEL
LOAD POWER TIMES
(off mains)
LOAD POWER TIME
(off battery)
102% < Load
≤
109%
Switches to bypass after 30 min
Shutdown after 30 min (if battery
back up time allows)
110% <= Load
≤
130%
Switches to bypass after 30 sec
Shutdown after 30 sec
130% < Load
≤
150%
Switches to bypass after 10 sec
Shutdown after 10 sec
Load > 150%
Switches to bypass after 0.5 sec
Shutdown after 0.5 sec
Short circuit
Immediate shutdown
Immediate shutdown