54
A
LARMS AND INDICATORS
UPS
FAILURE REPORTS TABLE
The following table describes the light and audio signals that appear/sound to indicate a fault.
Load level
Battery level
UPS Status
1 2 3 4 5 1 2 3 4 5
Mains
LED
Battery
LED
Bypass
LED
Battery
failure
LED
Failure/
Fault
LED
Audio
Alarm
Alarm phase
●
2 beeps
per sec.
Mains
overload
Switch over
to bypass
due to
overload
●
● ●
●
●
Battery
level
♦
●
●
continuo
us beep
Alarm phase
●
● ●
●
●
Battery
level
●
2 beeps
per
second
Battery
overload
Failure
●
●
continuo
us beep
Capacitor bank voltage fault
Load level
●
●
continuo
us beep
Output short circuit
Load level
●
●
●
continuo
us beep
Inverter fault
Load level
●
●
continuo
us beep
Overheating fault
Load level
●
●
continuo
us beep
Bypass
♦
●
●
Line
Load level
♦
●
Overloaded
Battery
fault
Standby
♦
♦ ♦ ♦ ♦
●
4 long
beeps at
1-second
intervals
Bypass
♦
♦
●
●
Line
Load level
●
♦
●
Battery
charge fault
Standby
♦
●
1 beep
per
second
Fan fault
Load level
●
●
●
1 beep
per
second
Input Relay fault
Load level
●
●
Continuo
us beep
●
LED on with steady light
♦
LED on with flashing light (1 flash per second).