background image

2509

7

GB

CONTROL BOX (See fig. 3)

COMBUSTION ADJUSTMENT

To suit the required appliance output, fit the nozzle, the settings of the combustion head and the
air damper opening in accordance with the following schedule. 

  

Nozzle

Pump

pressure

Burner

output

Comb. head

adjustment

Air damper adjustment

bar

kg/h ± 4%

1

st 

stage

2

nd 

stage

GPH

Angle

1

st

2

nd

1

st

2

nd

Set-point

Set-point

Set-point

1.35

60°

7

11

3.5

4.5

1.5

2.1

2.5

1.50

60°

7

11

4.2

5.2

1.5

2.5

3.1

1.75

60°

7

11

4.5

5.6

2.0

2.5

3.0

2.00

60°

7

11

5.7

7.1

3.0

2.8

3.5

2.25

60°

7

11

6.1

7.5

3.0

2.9

3.8

2.50

60°

7

11

6.5

8.2

3.5

3.0

4.2

2.75

60°

7

11

7.6

9.7

4.0

3.5

8.0

3.00

60°

7

10

8.3

10.1

6.0

3.6

8.0

 

NOZZLES RECOMMENDED: Monarch  type R

;

Delavan type B

Steinen 

type S - Q ;

Danfoss  type S

S7348

Ignition
transformer

Photoresistance

S7057

Fig. 3

To  remove  the  control-box  from  the  burner,  loosen  screw  (A)
and pull towards the arrow.

RUN OF THE ELECTRICAL CABLES
1
  - Cable grommet
2  - Cable-clamp
3  - Terminal block
4  - Clamps for 2

nd

 stage thermostat

5  - 4 pole socket for 2

nd

 stage thermostat

6  - 7 pole socket for burner
N  - Neutral

- Lock-out lamp

L  - Phase

- Burner-earth

The  photoresistance  is  fitted  directly  into  the
control  box  
(underneath  the  ignition-transformer)
on a plug-in support.

TESTING
Check  the  shut-down  of  the  burner  by  opening  the
thermostats.

FUEL  KEROSENE

RIELLO 40 G10D   TYPE  716 T81

3

1

2

1

Summary of Contents for G10D

Page 1: ...nstrucciones de instalaci n montaje y funcionamiento Kerosene and light oil burners Quemadores de kerosene y gas leo Two stage operation Funcionamiento de dos llamas CODE C DIGO MODELL MODELE MODEL MO...

Page 2: ......

Page 3: ...1 97 kWh kg Light oil viscosity 4 6 mm2 s at 20 C Hi 11 86 kWh kg Electrical supply Single phase 220V 10 15 60Hz Motor Run current 1 1A 3300 rpm 345 rad s Run current 2 15A 3250 rpm 340 rad s Capacito...

Page 4: ...rmal power kW D5815 60 70 80 90 100 0 2 0 6 Pressure in the combustion chamber mbar 6 7 9 10 8 110 1 0 1 2 3 7 3 2 0 1 6 4 6 8 Fuel output kg h 60 90 Thermal power kW D6122 120 150 180 210 240 0 8 2 4...

Page 5: ...ulating gasket Screws and nuts for flange Maintenance assembly Screw with two nuts for flange 7 pin plug 4 pin plug Flange Burner 305 108 261 140 40 4 5 262 1 1 204 D5670 189 83 83 170 4 5 105 RIELLO...

Page 6: ...ig 5 Remove the burner out of the boiler after loosing the fixing nut to the flange Hook the burner to the flange 1 by removing the combustion head 6 after loosing the fixing screws 7 Remove the diffu...

Page 7: ...priming Should lock out occur prior to the arrival of the fuel await at least 20 seconds before repeating the operation Check periodically the flexible pipes conditions Using kerosene they have to be...

Page 8: ...unter h WARNING DO NOT EXCHANGE THE NEUTRAL WITH THE PHASE NOTES Wires of 1 mm2 section The electrical wiring carried out by the installer must be in compliance with the rules in force in the Country...

Page 9: ...2 3 5 3 0 4 2 2 75 60 7 11 7 6 9 7 4 0 3 5 8 0 3 00 60 7 10 8 3 10 1 6 0 3 6 8 0 NOZZLES RECOMMENDED Monarch type R Delavan type B Steinen type S Q Danfoss type S S7348 Ignition transformer Photoresis...

Page 10: ...60 7 11 7 9 10 0 2 5 2 1 2 7 3 50 60 7 11 9 2 11 8 3 0 2 5 2 8 4 00 60 7 11 11 0 14 3 3 5 2 8 3 4 4 50 60 7 11 12 1 15 6 4 0 2 9 3 8 5 00 60 45 7 11 13 8 17 7 4 5 3 5 4 5 5 50 60 45 7 11 15 1 19 5 5 0...

Page 11: ...et point corresponds to 3 turns of the rod a hole 3 at its end facilitates counting the num ber of turns AIR DAMPER ADJUSTMENT The settings indicated in the schedule refer to the burner with its metal...

Page 12: ...re regulation this is set at 7 bar at the factory Should such pressure be reset or changed just turn the screw 4 The pressure gauge must be mounted in place of cap 5 2nd STAGE ADJUSTMENT Adjustment of...

Page 13: ...0 A A 0 5 mm MOVE THE ELECTRODE HOLDER BACKWARDS TO THE END Attention Before assembling or remov ing the nozzle loosen the screw A and move the elec trodes ahead TYPE 716 T81 717 T81 A 4 5 6 5 Normal...

Page 14: ......

Page 15: ...kg Gas leo viscosidad 4 6 mm2 s a 20 C Hi 11 86 kWh kg Alimentaci n el ctrica Monof sica 220V 10 15 60Hz Motor 1 1A absorbidos 3300 rpm 345 rad s 2 15A absorbidos 3250 rpm 340 rad s Condensador 2 5 F...

Page 16: ...encia t rmica kW D5815 60 70 80 90 100 0 2 0 6 Presi n en la c mara de combusti n mbar 6 7 9 10 8 110 1 0 1 2 3 7 3 2 0 1 6 4 6 8 Caudal de gas leo kg h 60 90 Potencia t rmica kW D6122 120 150 180 210...

Page 17: ...ercas para brida Conjunto mantenimiento Tornillo con dos tuercas para brida Conector macho de 7 contactos Conector macho de 7 contactos Brida Quemador 305 108 261 140 40 4 5 262 1 1 204 D5670 189 83 8...

Page 18: ...tornillos 2 y si es necesario las tuercas 3 interponiendo la protecci n aislante 5 ver Fig 4 POSICI N DE MANTENIMIENTO Accesibilidad al cabezal de combusti n al grupo disco estabilizador electrodos y...

Page 19: ...ula CEBADO DE LA BOMBA Encienda el quemador y espere el ce bado Si el bloqueo del quemador se produce antes de la llegada del com bustible esperar como m nimo 20 se gundos e iniciar de nuevo esta oper...

Page 20: ...s efectuadas por el instala dor deben cumplir la normativa vigente en el pa s Conectar el termostato 2a llama a los bornes T6 T8 eliminando el puente Verde C D A E C A D C D A C D B Electrov lvula 2 a...

Page 21: ...lograr el caudal requerido del aparato se debe determinar la boquilla la regulaci n del cabezal de combusti n y la regulaci n del registro del aire seg n la siguiente ficha Boquilla Presi n bomba Caud...

Page 22: ...50 60 7 11 9 2 11 8 3 0 2 5 2 8 4 00 60 7 11 11 0 14 3 3 5 2 8 3 4 4 50 60 7 11 12 1 15 6 4 0 2 9 3 8 5 00 60 45 7 11 13 8 17 7 4 5 3 5 4 5 5 50 60 45 7 11 15 1 19 5 5 0 3 5 5 5 BOQUILLAS ACONSEJADAS...

Page 23: ...la varilla Un orificio 3 en su extremo facilita contar las vueltas REGULACI N REGISTRO DEL AIRE La regulaci n indicada en la tabla se refiere al quemador con el envolvente montado y la c mara de combu...

Page 24: ...ci n presi n se ajusta a 7 bar en f brica Si tuviera que modificar o ajustar dicha presi n gire el tornillo 4 El man metro se debe montar en lugar de la tapa 5 REGULACI N 2a LLAMA Regulaci n del regis...

Page 25: ...5 mm RETROCEDER EL PORTAELECTRODOS HASTA EL TOPE Atenci n Antes de desmontar o mon tar la boquilla afloje el torni llo A y desplace hacia adelante los electrodos TIPO 716 T81 717 T81 A 4 5 6 5 Normal...

Page 26: ......

Page 27: ......

Page 28: ...Subject to modifications Con la posibilidad de modificaci n RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Reviews: