background image

20013749

GB

COMBUSTION ADJUSTMENT

In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjust-
ment and testing must be carried out observing the instruction manual of the boiler, including verifi-
cation  of  the  CO  and  CO

2

  concentration  in  the  flue  gases,  their  temperatures  and  the  average

temperature of the water in the boiler.

To suit  the required appliance  output,  fit  the nozzle then  adjust  the  pump  pressure,  the setting  of
the combustion head and the air damper opening in accordance with the following schedule.

The values shown in the table are measured on a CEN boiler (as per EN 267).
They refer to 12.5% CO

2

 at sea level and with light oil and room temperature of 20 °C

.

 

 

NOZZLES RECOMMENDED:

Monarch type R - NS;

Delavan type W - A - E;

Steinen type H - Q

;

Danfoss type H - B.

Angle

:

60° :

in most cases. 

80° :

in  case  of  flame  detachment,  during  ignitions  at  low  tem-

peratures.

 

PUMP PRESSURE

12 bar :

the pump leaves the factory set at this value

14 bar : improves  flame  retention;  it  is  therefore  suitable  for  ignitions

at low temperatures.

 

COMBUSTION HEAD SETTING

  

Nozzle

Pump pressure

Burner output

Comb. head 

adjustment

Air damper

adjustment

GPH

Angle

bar

kg/h ± 4%

Set-point

Set-point

0.40

80°

12

1.6

0

2.4

0.50

60°/ 80°

12

2.0

1

3.1

0.60

60°/ 80°

12

2.4

2

3.6

0.65

60°/ 80°

12

2.6

3

3.8

0.75

60°

12

3.0

4

4.0

SETTING CARRIED OUT IN THE FACTORY

0.65

60° W

12

2.6

2

2.1

1

2

3

4

1

2

3

This  is  done  when  fitting  the  nozzle,  with  the
blast tube removed.
It  depends  on  the  output  of  the  burner  and  is
carried out by rotating the regulating rod, till the
terminal plane of the blast tube is level with the
set-point, as indicated in the schedule.

In the sketch on the left, the combustion head
is  set  for  an  output  of  0.60  GPH  at  12 bar,
while  the  shutter  is  level  with  set-point  2,  as
required by the above schedule.

2

Blast tube

Regulating rod

Shutter

Terminal plane of the blast tube

D5322

1

3

5

Fig. 5

Summary of Contents for G3MC

Page 1: ...20013749 2 10 2009 Installation use and maintenance instructions Light oil burner CODE MODEL TYPE 20013629 G3MC 448T1 GB CN One stage operation...

Page 2: ...safety start up use and maintenance of the burner DELIVERY OF THE SYSTEM AND THE INSTRUCTION MAN UAL When the system is delivered it is important that The instruction manual is supplied to the user b...

Page 3: ...t oil viscosity 4 6 mm2 s at 20 C 1 5 E Electrical supply Single phase 230V 10 50Hz Motor Run current 0 7A 2850 rpm 298 rad s Capacitor 4 F Ignition transformer Secondary 8 kV 16 mA Pump Pressure 7 15...

Page 4: ...urner 125 110 194 130 26 4 5 89 213 11 162 D4673 180 75 72 150 4 5 125 It is necessary that the insulating gasket is placed between the boiler door and the burner flange This insulating gasket has six...

Page 5: ...leakage of the valve PRIMING THE PUMP Start the burner and wait for the prim ing Should lock out occur prior to the arrival of the fuel await at least 20 sec onds before repeating the operation A filt...

Page 6: ...burner Unscrew the fissing screws on the burner cover and remove it Unscrew the fissing screws 2 on the plate and remove the control box 1 Screw the two fissing screws 2 and reassemble the burner cov...

Page 7: ...e detachment during ignitions at low tem peratures PUMP PRESSURE 12 bar the pump leaves the factory set at this value 14 bar improves flame retention it is therefore suitable for ignitions at low temp...

Page 8: ...nting the number of turns AIR DAMPER ADJUSTMENT see fig 7 The mobile air damper A operated by the jack B as sures the complete opening of the air intake The regulation of the air rate is made by adjus...

Page 9: ...to 14 bar 4 COMBUSTION HEAD SETTING Regulate the combustion head one set point further ahead than indicated in the instructions Example the instructions require to set the combustion head on set point...

Page 10: ...ion areas and in the combustion product waste pipe Clean the filter in the oil suction line and in the pump Check for correct fuel consumption Check that the burner electrical connections are correct...

Page 11: ...20013749 CN Technical Assistance Centre Assistance Centre Maintenance Contract...

Page 12: ...1 20013749 CN 2 1 4 3 1 448T1 19 35 kW 1 6 3 kg h 20 C 4 6 mm2 s 1 5 E 230V 10 50Hz 0 7A 2850 rpm 298 rad s 4 F 8 kV 16 mA 7 15 bar 0 115 kW 1 2 3 4 5 6 7 8 9 10 11 1 8 D4672 9 10 2 7 1 3 4 5 6 11...

Page 13: ...20013749 2 CN 0 8 0 0 2 0 4 m m m m b b b b a a a a r r r r 1 5 2 2 5 3 kg h 20 25 30 35 kW D5223 0 6 125 110 194 130 26 4 5 89 213 11 162 D4673 180 75 72 150 4 5 125 6 6 2 D5242 D5218 2 S7387...

Page 14: ...r 30 cm Hg 20 H L I D 8 mm I D 10 mm 0 5 1 1 5 2 10 20 40 60 20 40 80 100 A 3 A H L I D 8 mm I D 10 mm 0 0 5 1 1 5 2 3 3 5 35 30 25 20 15 8 6 100 100 100 90 70 30 20 H 4 m H H 4 m 0 1 m D5219 D5220 D5...

Page 15: ...20013749 4 CN 1mm2 4 1 2 1 2 1 Fig 4 2 1 D4677 A 530SE C E F FR P E H I M PE TL TS XP Y...

Page 16: ...R NS Delavan W A E Steinen H Q Danfoss H B 60 80 12 bar 14 bar GPH bar kg h 4 0 40 80 12 1 6 0 2 4 0 50 60 80 12 2 0 1 3 1 0 60 60 80 12 2 4 2 3 6 0 65 60 80 12 2 6 3 3 8 0 75 60 12 3 0 4 4 0 0 65 60...

Page 17: ...20013749 6 CN 6 6mm 2 6 1 6 6 6 6 CO2 CO2 3 1 3 6 6 6 6 7 A B C D D A 0 1 2 3 6 D5323 6 D C D5786 D A B 7 4 A 2 2 5 mm 4 0 3 mm D5230 A 8...

Page 18: ...7 20013749 CN 8 C 1 8 2 Delavan A E Steinen H Danfoss H 3 12 bar 8 C 14 bar 4 2 3 5 Bacharach 1 12 D5229 12 5...

Page 19: ...20013749 8 CN CO2 CO ppm NOx ppm...

Page 20: ...I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com Manufacturing site Riello Heating Equipment Shanghai CO LTD No 388 Jinbai Road Jinshan Industrial Zone 201506 Shang...

Reviews: