20013756
6
GB
GAS TRAIN ACCORDING TO EN 676
The gas train is supplied separately, for its adjustment see the enclosed instructions.
CONNECTION OF PRESSURE TAPS TO GAS TRAIN
GAS TRAIN
MATCHED
BURNER
CONNECTIONS
USE
TYPE
CODE
INLET
OUTLET
MB-VEF 407 B01
3970535
GS10-20/M
Rp 3/4
Rp 3/4
Natural gas and LPG
MB-VEF 412 B01
3970536
GS20/M
Rp 3/4
Rp 3/4
Natural gas high capacity
120 kW
Connect proceeding as follows:
Secure the three G1/8 connectors (one supplied
with the burner and two with the train) at points
A
,
Pf
and
Pl
.
Secure the M12 connector at point
B
.
Cut the pipe supplied with the burner into equal
halves.
Connect boiler tap
A
with valve tap
Pf
and sleeve
tap
B
with valve tap
Pl
using the previously cut
pipes.
A
B
Pf
Pl
D4272