TROUBLESHOOTING 

 

PROBLEM 

POSSIBLE 

CAUSE 

PROCEDURE 

The UPS does not 

switch on 

The UPS is switched 

off 

Check that the STAND-BY/ON switch is in the ON 

position 

The UPS input thermal 

protection device has 

been triggered  

Disconnect non-essential equipment from the UPS. 

Reset the protection (11) by depressing the button. If 
the switch resets, start up the UPS and reconnect the 

equipment one device at a time. If the protection 

activates again, one of the connected devices is 

causing an overload condition. 

The UPS is working on 

battery even though 

mains power is 

available  

The UPS input 

thermal protection 

device has been 

triggered  

Disconnect non essential equipment from the UPS. 
Reset the protection (11) by depressing the button. 

The mains power 

supply socket the UPS 

is connected to is not 

supplying power to the 

device 

Connect the UPS to another mains power supply 

socket or have the mains supply checked by a 

qualified electrician. 

When there is a mains 

power supply failure, 

the UPS does not work 

for the expected 

runtime 

The UPS battery is 

not sufficiently 

charged as there was 

not enough time for it 

to recharge after a 

recent power failure 

Wait for the battery to recharge. It recharges each time 

the UPS is connected to a mains socket. It usually 

takes 8 hours for the battery to recharge fully. UPS 

operation time is a function of how charged the 

battery is. 

The battery needs to 

be replaced. 

Replace the battery. 

The alarm icon (3) is lit 

and the acoustic signal 

sounds. 

The UPS has a fault. 

Remove the external devices from the UPS. Turn off 

the UPS and disconnect it from the mains. Connect 
the UPS to the mains and turn on again. If the UPS 

message the anomaly again, contact your authorized 

service centre. 

Battery fault message. 

Battery fault. 

Replace the battery. 

The UPS is not 

communicating with a 

PC. 

The software sends a 

message that 

communication has 

been lost. 

Check that the USB cable is connected between the 

UPS and the PC and that ‘USB’ has been selected as 

the communication port in the software configuration.

The software is not 

installed 

Install the specific software for your computer’s 

operating system. 

 
 

TECHNICAL DATA 

 

MODEL 600VA 

800VA 

INPUT 

Voltage 

230V +20%/ -25% 

Frequency 

50 or 60Hz +/-5% (with auto-sensing) 

OUTPUT 

Voltage (from battery) 

/-10% (Pseudo-sinusoidal wave) 

Frequency (from battery)

50 or 60Hz +/-1Hz (with auto-sensing) 

Trigger time 

2-6 ms typical 

Rated power VA 

600 

800 

Rated power W 

360 

480 

SURGE 

SOCKETS 

Max. current 

5A 

8A 

PROTECTION 

DEVICES AND 

FILTERS 

Overload and shortcircuit 

protection 

From mains: overload input protection. 

From mains: automatic shutdown after 5 minutes with load 

>110% and immediate shutdown with load >120% or for 

shortcircuit. 

From battery: automatic shutdown after 5 seconds with load 

>110% and immediate shutdown with load >120% or for 

shortcircuit. 

BATTERY 

Type 

Sealed lead batteries, maintenance-free 

Model 

12V 7Ah 

12V 9Ah 

Typical recharge time 

6-8 hours 

Protection 

Protection against total discharge, battery  replacement 

indicator 

AMBIENT 

CONDITIONS 

Operating conditions 

Max altitude 6,000 m, 0-90% non condensing humidity, 

0-40°C 

VARIOUS 

Noise 

<40dB (at 1m from source) 

Earth leakage current 

<1mA 

 

  RISOLUZIONE PROBLEMI

 

 

PROBLEMA 

POSSIBILE 

CAUSA 

PROCEDURA 

L’UPS non si accende. 

L’UPS è spento. 

Verificare che l’interruttore STAND-BY/ON sia in 

posizione ON. 

È scattata la protezione 

d’ingresso dell’UPS. 

Scollegare gli apparecchi non essenziali dall'UPS. 

Ripristinare la protezione (11) premendo il relativo 

pulsante fino al blocco. Accendere l'UPS e ricollegare 

gli apparecchi uno alla volta. Se la protezione 
interviene di nuovo, probabilmente uno degli 

apparecchi collegati è la causa del sovraccarico. 

L'UPS funziona da 

batteria sebbene sia 

disponibile la rete 

elettrica. 

È scattata la protezione 

d’ingresso dell'UPS. 

Scollegare gli apparecchi non essenziali dall'UPS. 

Ripristinare la protezione (11) premendo il relativo 

pulsante fino al blocco. 

La presa di 

alimentazione a cui è 

collegato l’UPS non 

fornisce alimentazione al 

dispositivo. 

Collegare l'UPS a un’altra presa di alimentazione o far 

controllare l’impianto di rete da un elettricista 

qualificato. 

Quando si verifica un 

guasto della rete 

elettrica l'UPS non 

funziona per il periodo 

di tempo previsto. 

La batteria dell'UPS non 

è adeguatamente carica 

in quanto non ha avuto il 
tempo di ricaricarsi dopo 

una recente mancanza 

della rete elettrica. 

Attendere che la batteria si ricarichi. La ricarica 

avviene ogni qualvolta l'UPS è collegato a una presa di 
alimentazione. In genere occorrono 8 ore per ricaricare 

completamente la batteria. Il tempo di funzionamento 

dell'UPS da batteria è ridotto finché la batteria non è 

completamente carica. 

La batteria è da 

sostituire. 

Sostituire la batteria. 

Il simbolo di allarme 

(3) si accende e il 
segnale acustico è 

attivo. 

L’UPS ha rilevato 

un’anomalia. 

Scollegare gli apparecchi dall’UPS. Spegnere l’UPS e 

togliere l’alimentazione. Alimentare l’UPS e 

riaccenderlo nuovamente. Se la segnalazione si 

ripresenta rivolgersi al vostro centro di assistenza 

autorizzato. 

Si attiva la 

segnalazione di 
batteria guasta. 

Batteria guasta. 

Sostituire la batteria. 

L’UPS non comunica 

con il pc. 

Il software manda un 

messaggio di 

comunicazione persa. 

Controllare che il cavo USB sia collegato all’Ups e al 

pc e che nella configurazione del software di 

comunicazione sia selezionata USB come porta di 

comunicazione. 

Il software non è 

installato 

Installare il software specifico per il sistema operativo 

del vostro pc. 

 
 
 
DATI TECNICI 

 

MODELLO 600VA 

800VA 

INGRESSO 

Tensione 

230V +20%/ -25% 

Frequenza 

50 or 60Hz +/-5% (con autoapprendimento) 

USCITA 

Tensione (da batteria) 

/-10% (Onda pseudo sinusoidale) 

Frequenza (da batteria) 

50 or 60Hz +/-1Hz (con autoapprendimento) 

Tempo di intervento 

Tipico 2-6 ms 

Potenza nominale VA 

600 

800 

Potenza nominale W 

360 

480 

PRESE SURGE 

Corrente max. 

5A 

8A 

PROTEZIONE  

Protezione sovraccarico e 

cortocircuito 

Da Rete: protezione d’ingresso per sovraccarico. 

Da Rete: spegnimento automatico dopo 5 minuti con carico 
>110% e immediato con carico >120% o con cortocircuito. 

Da Batteria: spegnimento automatico dopo 5 secondi con 

sovraccarico >110% ed immediato con sovraccarico >120% o 

con cortocircuito. 

BATTERIA 

Tipo 

Sigillate, al piombo, senza manutenzione 

Modello 

12V 7Ah 

12V 9Ah 

Tempo di ricarica tipico 

6-8 ore 

Protezioni 

Protezione contro la scarica totale, indicatore di sostituzione 

batteria 

CONDIZIONI 

AMBIENTALI 

Condizioni operative 

Altitudine max 6,000 m, 0-90% di umidità non condensata, 0-

40°C 

VARIE 

Rumorosità 

<40dB (a 1 m dalla sorgente ) 

Correnti di dispersione 

verso terra 

<1mA 

 

 

 
Thank you for choosing our product. 

 
 

IMPORTANT SAFETY NOTES 

 

This device can be installed by anyone, provided that they READ THIS MANUAL CAREFULLY 
AND FOLLOW THE INSTRUCTIONS WITHIN IT. 
This manual contains detailed instructions for the use and installation of the UPS.  
This manual should be kept close to the UPS and READ BEFORE  THE UPS IS INSTALLED 
AND USED 

 

© No part of this manual may be reproduced, even partially, without the manufacturer’s 
authorisation. For purposes of improvements the manufacturer reserves the right to change 
specifications at any time and without notice. 

 
 

      Warning: 

Read the following instructions carefully and keep this manual handy for easy referral. 
The mains power supply socket used to power the UPS must have an earth connection. 
Potentially dangerous electrical voltages are generated inside this device, even when the UPS is 
switched off. All repairs must be carried out by authorised personnel only. 
Voltage may be present on the UPS output sockets even when the UPS is not connected to a mains 
power supply. 
In the event of a mains power supply failure (emergency UPS operation), do not unplug the power 
supply cable to the UPS, to ensure earth continuity to the connected loads. 
Do not allow liquids and/or other foreign bodies to enter the UPS. 
Since the mains power supply cable acts as a separation device, the mains power supply socket 
used that connects to the rear of the UPS must be accessible and easy to disconnect. 
In dangerous conditions and/or to disconnect the UPS from sources of energy, (whether mains or 
batteries), disconnect the power supply cable from the mains socket or from the back of the UPS 
and shut down the UPS using the STAND-BY/ON switch (6). 
Risk of electric shock. Since internal components are connected to the batteries, they will remain 
powered, and therefore dangerous, even after the device has been disconnected from a mains power 
supply. Disconnect the batteries and ensure no voltage is present before carrying out any repair or 
maintenance operations. 
The UPS generates an earth leakage current. Ensure that the sum of the UPS and load earth leakage 
current is less than 3.5mA. 
Replaced batteries should be considered as TOXIC WASTE and treated as such. 
Do not throw the batteries into a fire. 
Do not try to open the batteries: they do not require any maintenance. Furthermore the electrolyte is 
dangerous if it comes into contact with skin or eyes and may be toxic. 
The batteries can cause electric shock and have a high short circuit current. Take the necessary 
safety measures and precautions when handling them: 

-  do not wear watches, rings, necklaces or any other metallic material 
-  only use tools with insulated handles 

Only use the UPS following the specific instructions in this user manual. 

 
 
 

DESCRIPTION OF THE UPS 

 

Front and rear views: 

1.

 

Back-up sockets (local type) 

2.

 

Surge sockets (local type) 

3.

 

/RED LED: various messages (see the “Alarms and Report Signals table”) 

4.

 

/YELLOW LED: the UPS operates on battery 

5.

 

/GREEN LED: the UPS operates from the mains power supply 

6.

 

Main STAND-BY/ON switch 

7.

 

Battery compartment locking screws 

8.

 

Battery compartment 

9.

 

Back-up sockets (IEC type) 

10.

 

USB port 

11.

 

Input protection device 

12.

 

Power supply cable 

 
 
 

INSTALLATION 

 

Opening of packing and verification of its contents 

Remove the UPS from its packaging and check that there is no visible damage caused during 
shipping. If there is any noticeable damage to the UPS, pack the product up and return to 
where it was purchased. 

 

Packing contents 

¾

 

UPS 

¾

 

User manual 

¾

 

Warranty card 

 
 

Positioning 

Follow the instructions below to correctly install and position the UPS:

 

¾

 

The UPS must be placed on a horizontal surface. 

¾

 

The UPS must not be exposed to direct sunlight. 

¾

 

Ensure that the ambient temperature is between 0°C and 40°C, for optimal performance use 
at a maximum temperature of 25°C. 

¾

 

The ambient humidity is less than 90%. 

¾

 

Avoid dusty environments. 

¾

 

Place the UPS at least 5cm from a wall to ensure adequate ventilation. 

¾

 

Ensure that the UPS or any other heavy object is clear of the power supply cable. 

¾

 

Ensure that the cables connecting loads to the UPS are not longer than 10metres. 

 
 

Storage 

The UPS must be fully recharged if it is to be stored for a long time. A full discharge and charge 
cycle should be carried out every 6 months to keep the battery in good condition. 

OPERATION 

 

Connection to mains and battery charging 

Please ensure that the mains power supply to be used with this UPS has upstream protection rated 
at either 10A. 

¾

 

Connecting the UPS to the mains with the power supply cable provided. 

¾

 

The UPS will recharge its battery each time it is connected to a mains power supply (even if 
it is powered down). We recommend that the UPS is charged for 6-8 hours before connecting 
the loads. 

 
 
 

Connecting the loads 

After having loaded the UPS, loads can be connected (e.g.: computer, monitor, etc.) to the output 
sockets, according to the following indications:

 

¾

 

Back-up sockets (1) (9)

: these sockets are only powered when the UPS is on. Should mains 

power fail, the back-up sockets are battery-powered. 

 

N.B.: 

we recommend not running laser printers or laser print devices from back-up sockets 

(1) (9) together with other computer peripheral equipment. On odd occasions, this equipment 
uses a greater quantity of energy than when at rest. This set-up may lead to UPS overload and 
cause all equipment connected to be switched off.

 

¾

 

Surge sockets (2):

 additional filtered sockets limiting line surge and mains disturbances. 

They do not protect the load from power failures or short blackouts.

 They can be used to 

power non-essential devices such as, for example, printers, scanners and suchlike. Small 
laser printer devices can be installed on these sockets. 

 

N.B.:

 the sockets are also powered when the UPS is in stand-by. 

 

 
 
 

Starting up/Shutting down 

Press the main STAND-BY/ON switch to start-up the UPS and power the loads. 
Press the switch again to shut down the UPS and power down from the loads. 

 
 
 

Starting up on battery (Cold start)

 

If there is no mains power supply present, pressing the main power switch will cause the UPS to 
start up using its battery as a source of power. 

      Warning:

 when starting up on battery, the output frequency is set to 50Hz.

 

 
 
 

USB port 

The UPS can be connected to a computer for remote monitoring and shutdown operations using a 
USB cable. The UPS management software and related manual can be downloaded from 
www.riello-ups.com. 

 
 
 

Replacing the batteries 
CAUTION: The models require replacement by qualified service personnel. 
Contact technical support for information concerning the exact model of battery to use. 
 

-

 

Shut down the UPS and disconnect the power cable. Remove the screws that hold the battery 
compartment in place under the UPS. (Fig. 

A

 
-

 

After removing the cover, carefully remove the battery from its housing. (Fig. 

B

 
-

 

Disconnect the two wires from the battery  (simply by pulling them). Replace the battery with 
another of the same type, taking care to respect the polarity. Re-assemble the compartment. (Fig. 

C

 
 
 

ALARMS AND REPORT SIGNALS 
 

Description

 

Switch 

position 

(6)

 

Led functioning

 

Other report signals

 

Green led 

 

Yellow led 

 

Red led 

 

Stand-by STAND-BY  

  Blinking 

 

 

Operation on mains 

power 

ON Steady   

 

 

Operation on battery 

ON 

 

Blinking 

 

Slow blinking acoustic 

signal 

End of discharge 

warning 

ON 

 

Blinking 

 

Blinking acoustic signal

Overload 

ON 

 

 

Blinking 

Blinking acoustic signal

Battery fault 

ON 

Steady 

 

Steady 

Blinking acoustic signal 

Alarm or fault (other 

than overload) 

ON    

Steady 

Continuous acoustic 

signal 

 

 

 

Vi ringraziamo per la scelta del nostro prodotto! 

 
 

NOTE IMPORTANTI PER LA SICUREZZA 

 

Questa apparecchiatura può essere installata da qualsiasi persona, previa ATTENTA E 
SCRUPOLOSA LETTURA DEL PRESENTE MANUALE. 
Questo manuale contiene le istruzioni dettagliate per l’uso e l’installazione dell’UPS.  
Per informazioni sull’utilizzo e per ottenere il massimo delle prestazioni dalla Vostra 
apparecchiatura, il presente manuale dovrà essere conservato con cura vicino all’UPS e 
CONSULTATO PRIMA DI OPERARE SULLO STESSO. 

 

© E’ vietata la riproduzione di qualsiasi parte del presente manuale anche se parziale salvo 
autorizzazione della ditta costruttrice. Per scopi migliorativi, il costruttore si riserva la facoltà di 
modificare il prodotto descritto in qualsiasi momento e senza preavviso. 

 

      

Attenzione: 

Leggere con cura le seguenti istruzioni e tenere a disposizione questo manuale per una rapida 
consultazione. 
La presa di rete cui l’UPS è collegato deve essere dotata di connessione di terra. 
All’interno di questa apparecchiatura vi sono tensioni potenzialmente pericolose, anche con UPS 
spento. Tutte le riparazioni dovranno essere effettuate esclusivamente da personale autorizzato. 
Le prese di uscita dell’UPS potrebbero essere in tensione anche quando l’UPS non è collegato alla 
rete. 
In caso di mancanza di rete (funzionamento dell’UPS da batteria), non staccare il cavo di 
alimentazione per garantire la continuità di terra all’utenza collegata. 
Evitare che liquidi e/o altri corpi entrino nell’UPS. 
Poiché il cavo di alimentazione separabile è inteso come dispositivo di sezionamento, la presa di 
rete cui l’UPS è collegato e/o il retro dell’UPS devono essere accessibili e facilmente scollegabili. 
In condizioni di pericolo e/o per scollegare l’UPS dalle sorgenti di energia, rete e batterie, 
sconnettere il cavo di alimentazione dalla presa di rete o dal retro dell’UPS e spegnere tramite 
l’interruttore STAND-BY/ON (6). 
Rischio di scossa elettrica. Anche dopo aver scollegato l’apparecchiatura dalla rete elettrica di 
alimentazione, i componenti interni dell’UPS essendo collegati alle batterie, sono ancora in 
tensione, quindi pericolosi. Prima di effettuare qualsiasi tipo di riparazione o manutenzione, 
scollegare le batterie e verificare che non sia presente tensione. 
L’UPS genera una corrente di dispersione. Assicurarsi che la somma della corrente di dispersione 
verso terra dell’UPS e del carico connesso sia inferiore del limite di 3,5mA. 
Le batterie sostituite vanno considerate RIFIUTO TOSSICO e trattate di conseguenza. 
Non gettare le batterie sul fuoco. 
Non tentare di aprire le batterie: sono prive di manutenzione. Il liquido elettrolita è pericoloso per la 
pelle e per gli occhi, e può risultare tossico. 
Le batterie possono essere causa di scossa elettrica e sono dotate di un alta corrente di cortocircuito. 
Prendere le necessarie precauzioni e misure di sicurezza, di seguito elencate, quando si maneggiano 
delle batterie: 

-  non indossare orologi, anelli, catenine o qualsiasi altro materiale metallico 
-  usare solo attrezzi con impugnatura isolata 

Usare l’UPS seguendo le specifiche previste secondo quanto prescritto dal presente manuale d’uso. 

 
 

DESCRIZIONE DELL’UPS 

 

Viste frontali e posteriori: 

 

1.

 

Prese di backup (tipo locale) 

2.

 

Prese Surge (tipo locale) 

3.

 

/LED ROSSO: segnalazioni varie (vedi tabella “Allarmi e segnalazioni”) 

4.

 

/LED GIALLO: UPS in funzionamento da batteria 

5.

 

/LED VERDE: UPS acceso con rete presente 

6.

 

Interruttore principale STAND-BY/ON 

7.

 

Vite bloccaggio vano batteria 

8.

 

Vano batteria 

9.

 

Prese di backup tipo IEC 

10.

 

Porta USB 

11.

 

Protezione di ingresso 

12.

 

Cavo di alimentazione 

 
 

INSTALLAZIONE 

 

Apertura dell’imballo e verifica del suo contenuto 

Rimuovere l’UPS dall’imballo e verificare che non vi siano danni visibili causati durante il 
trasporto. Qualora si notassero danni all’UPS reimballare il prodotto e restituire presso il centro di 
acquisto. 

 
 

Contenuto dell’imballo 

¾

 

UPS 

¾

 

Manuale d’uso 

¾

 

Cartolina Garanzia 

 
 

Collocazione 

Seguire le seguenti indicazioni per installare e posizionare correttamente l’UPS: 

¾

 

L’UPS deve essere posto su di un piano orizzontale 

¾

 

L’UPS non deve essere esposto alla luce diretta del sole 

¾

 

Assicurarsi che la temperatura dell’ambiente sia compresa tra 0°C e 40°C, per un 
funzionamento ottimale utilizzare a una temperatura massima di 25°C. 

¾

 

Il tasso di umidità dell’ambiente deve essere inferiore al 90% 

¾

 

Evitare ambienti polverosi 

¾

 

Posizionare l’UPS almeno a 5 cm di distanza dai muri circostanti al fine di permettere 
un’adeguata aerazione 

¾

 

Assicurarsi che ne l’UPS ne qualche altro oggetto pesante schiacci il cavo di alimentazione 

¾

 

Il cavo che connette i carichi all’UPS non deve superare i 10 metri di lunghezza 

 
 

Immagazzinamento 

È necessario ricaricare completamente l’UPS se necessita di un lungo periodo di 
immagazzinamento. Ogni 6 mesi effettuare un ciclo di scarica e carica completa per conservare in 
buono stato la batteria. 

FUNZIONAMENTO

 
 

Collegamento alla rete e carica delle batterie

 

Verificare che nell’impianto a monte dell’UPS vi sia una protezione da sovracorrenti. Il valore della 
protezione consigliata è di 10A. 

¾

 

collegare l’UPS alla rete elettrica tramite il cavo di alimentazione fornito in dotazione. 

¾

 

L’UPS effettua la ricarica della batteria ogni qualvolta viene collegato all’alimentazione di 
rete (anche se spento). Caricare per 6-8 ore l’UPS prima di collegare i vari carichi. 

 
 

Connessione dei carichi 

Dopo aver caricato l’UPS è possibile collegare i diversi carichi (es: computer, monitor, ecc…) alle 
prese presenti sull’UPS. 

¾

 

Prese Backup (1)(9

):queste prese sono alimentate solo quando l’UPS è acceso. In caso di 

mancanza rete le prese di backup sono alimentate tramite batteria.  

Nota: 

si consiglia di non applicare stampanti laser o dispositivi di stampa a laser sulle prese 

di backup (1)(9) assieme ad altre periferiche del computer. Queste apparecchiature assorbono 
occasionalmente una quantità maggiore di energia rispetto a quando sono a riposo. Questa 
configurazione potrebbe portare in sovraccarico l’UPS e allo spegnimento di tutte le 
apparecchiature collegate. 

¾

 

Prese Surge (2):

 prese addizionali filtrate, limitano le sovratensioni e disturbi di rete; 

non 

proteggono il carico dagli eventi di mancanza rete o brevi interruzioni.

 Possono essere 

utilizzate per alimentare dispositivi non essenziali quali ad esempio stampanti, scanner o 
altro. Su queste prese è possibile installare piccoli dispositivi di stampa a laser. 

 

Nota:

 le prese sono alimentate anche quando l’UPS è in stand-by.  

 
 

Accensione/Spegnimento 

Premere l’interruttore principale STAND-BY/ON per accendere l’UPS ed alimentare i carichi. 
Per spegnere l’UPS e togliere l’alimentazione ai carichi premere nuovamente l’interruttore 
principale. 

 
 

Accensione da batteria (Cold start)

 

In caso di assenza di rete, premendo l’interruttore principale, l’UPS effettua l’accensione da 
batteria. 

 

Attenzione: 

quando viene effettuata l’accensione da batteria la frequenza di uscita è impostata 

a 50Hz.

 

 
 

Porta USB 

L’UPS può essere collegato tramite un cavo di collegamento USB ad un computer per funzioni di 
monitoraggio e shutdown del sistema operativo. È possibile scaricare il software di gestione ed il 
relativo manuale dal sito internet www.riello-ups.com. 

 
 
 

Sostituzione della batteria 
ATTENZIONE:La sostituzione delle batterie deve essere effettuata esclusivamente da personale qualificato. 
Contattare l'assistenza tecnica per informazioni relative al modello esatto di batteria da utilizzare.  

 
-

 

Spegnere l’UPS e scollegare il cavo di alimentazione. Rimuovere le viti che fissano il vano 
batterie situate sotto L’UPS (Fig. 

A

 
-

 

Dopo aver rimosso il coperchio, rimuovere con delicatezza la batteria dal proprio alloggiamento 
(Fig. 

B

 
-

 

Scollegare quindi i due fili dalla batteria (semplicemente tirandoli). Sostituire la batteria con una 
dello stesso tipo facendo molta attenzione a 

rispettare la polarità

. Riassemblare il tutto (Fig. 

C

 

 
 
 

ALLARMI E SEGNALAZIONI 

 
 

Descrizione

 

Posizione 

interruttore 

(6)

 

Funzionamento Led

 

Altre segnalazioni

 

Led Verde 

 

Led Giallo 

 

Led Rosso 

 

Stand-by STAND-BY   

 Intermittente

 

Funzionamento 

da rete 

ON Fisso   

 

 

Funzionamento 

da batteria 

ON  

Intermittente

 

Segnale acustico 

intermittente lento 

Preavviso di fine 

scarica 

ON  

Intermittente

 

Segnale acustico 

intermittente 

Sovraccarico ON 

 

 

Intermittente

Segnale acustico 

intermittenti 

Batteria guasta 

ON 

Fisso 

 

Fisso 

Segnale acustico 

intermittente 

Allarme o blocco 

(diverso dal 

sovraccarico) 

ON    

Fisso 

Segnale 

acustico 

continuo 

 