Activation 2 menu
/------------------------/
/ Activation 2 /
/------------------------/
Enable Serial N:
[
ON
/off]
<--
Enable Sensors.:
[
ON
/off]
Enable WOL :
[on/
OFF
]
With this menu the services implemented in
NetMan plus
can be activated or deactivated:
Use the ENTER key to change the selected
configuration (“ON” or “OFF”).
ON (green characters): service active
OFF (red characters): service not active
It is recommended to activate only the services used.
Sensors Config menu
To enter on the “Sensors config” menu is necessary to enable the “Sensors” service
(Activation 2 menu) and to save the configuration (Save and load menu).
Sensors Devices
Press [C] to change sensors, [E] to exit
Enter on the “Config sensor” menu, connect the first sensor and press “C”. After some instants the
device will be recognized and the device will be given an identifier number [1]. Connect the next
sensor, if present, and press “N”. After some instants the device will be recognized and the device
will be given an identifier number [2]. Repeat the procedure for all the sensors and when the
configuration is finalized press “Y”.
Sensors Devices
[1] Sensor Digital I/O
+ Temperature (140000009A204C28)
+ Digital I/O (220000003B8C9F12)
+ 1 Input
+ 1 Output
[2] Sensor Digital I/O
+ Temperature (510000009A154228)
+ Digital I/O (BB0000003BA2FF12)
+ 1 Input
+ 1 Output
[3] Sensor Temperature (F100000013BE0628)
+ Temperature
[4] Sensor Temperature (6C0000009F6D6128)
+ Temperature
[5] Sensor Humidity (4D00000083FF3326)
+ Humidity
+ Temperature
Press [Y] to confirm, [N] to insert a new sensor
For proper working of the devices, it is necessary to add just one device for each iteration
and wait that it is recognized by
NetMan plus
.