I/O Sensors menu
/------------------------/
/ Output /
/------------------------/
UPS Lock.......:
-<--
Ovrload/Ovrtemp:
-
UPS Failure....:
-
On bypass......:
4
Battery work...:
3
Battery low....:
-
Communic lost..:
-
Input sensor...:
1
Press [Esc] to quit
With this menu is possibile to associate a digital output of the installed sensors to one or more
events of the UPS. The output will be closed when the associated event happens.
Press ENTER to select the output.
The identification number is the same which is associated to the sensor during
installation.
The following table describes the meaning of the events. These can vary depending on the UPS
connected.
Event
Description
UPS Lock
UPS is locked
Ovrload/Ovrtemp
UPS in overload or in overtemperature
UPS Failure
Failure of the UPS
On bypass
Operation from bypass
Battery work
Operation from battery
Battery low
Battery low
Communic lost
Communication between the UPS and the device has been interrupted
The “Input sensor” event allows to associate a digital output with the digital input of the
Digital I/O &
Temperature
sensor which is installed with the lowest identification number (
the first that was
detected during configuration
). The state of the input (open/closed) is reported to the output of
the selected sensor.